&DOFXODWLQJWKH0D[LPXP6HFRQGDU\3RZHU)LUH$ODUP&XUUHQW
'UDZ
Use Table G-3 to determine the maximum current requirements of secondary power
source during fire alarm conditions. The result obtained from Table G-3 is the amount
of current that the batteries must be able to supply to the fire alarm system. Use the
result in Table G-4 to determine the size of the batteries needed for the fire alarm
system.
Results taken from Table G-3 assume that, while in a fire alarm condition, batteries
must feed the main power supply (and any additional supplies such as the AVPS-24 and
AA-30) with the maximum rated power each supply can provide.
On a system with a power supply having a small load, you can calculate the exact alarm
current requirements of the secondary supply. To do so, add the secondary Non-Fire
Alarm Load (from Table G-2) to the total fire alarm current draw of all notification
appliances in the system. Use this value in Table G-4.
No. in Alarm
Device
(Simultaneously)
MPS-400
1
AVPS-24
[ ]
AA-30
[ ]
AA-120
[ ]
7DEOH * 0D[LPXP 6HFRQGDU\ 3RZHU )LUH $ODUP &XUUHQW 'UDZ
Calculating the System Current Draws
Multiply
Current
by
(in amps)
X
6
X
3
X
3
X
7.3
Sum Column for Secondary Fire Alarm Load =
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97