Wiring 2-Wire Smoke Detector; Figure 4. 4-Wire Smoke Detector Connections - ADEMCO 5110XM Installation Instructions Manual

Microprocessor-based fire alarm control/communicator
Hide thumbs Also See for 5110XM:
Table of Contents

Advertisement

Remove 2000 ohm EOL resistor if connected across the zone terminals, and
connect it across the loop wires at the last detector.
3. To supervise power, you MUST use a UL listed End-Of-Line Power
Supervision Relay (i.e. System Sensor No. A77-716B).
POWER
DETECTORS
UL LISTED
COMPATIBLE
CONTROL
ZONE
TERMINALS
1412
2412
2412TH
2112/24T
Wiring 2-Wire Smoke Detectors To Zone 5
1. Connect up to 16 of the 2-wire smoke detectors listed below across zone 5
terminals 15 (+) and 16 (–). Observe proper polarity when connecting the
detectors.
2. Connect the EOL resistor at the last detector.
3. See "Programming Hard-Wired Zones" later in this section for a detailed
programming procedure.
Due to the alarm current available on zone 5, only one smoke detector at a
time can be supported in the alarmed state.
+
7
TO
-
18
+
PANEL
+
-
Four-Wire Detector Circuit
Figure 4: 4-Wire Smoke Detector Connections
COMPATIBLE 4-WIRE SMOKE/COMBUSTION DETECTORS
System Sensor, 4-wire ionization products of combustion
detector
System Sensor, 4-wire photoelectric smoke detector
System Sensor, 4-wire photoelectric smoke detector
w/135º F (57º C) heat detector
System Sensor low-profile 4-wire photoelectric smoke detector
w/135º F (57º C) heat detector
– 18–
-
4-WIRE SMOKE
DETECTORS
+
-
-
HEAT
DETECTOR
+
EOL
POWER
SUPERVISION
RELAY
MODULE
A77-716B
2000Ω
EOLR