ADEMCO 5110XM Installation Instructions Manual page 52

Microprocessor-based fire alarm control/communicator
Hide thumbs Also See for 5110XM:
Table of Contents

Advertisement

↓ Zone Number
01 Zone Type
Fire
09
Zone Type
01 Report Code
1st 00 2nd 00
00
Typical Summary Display
Zn ZT
RC
01
09
3C
Accepted report code
Program Alpha?
0 = No 1 = Yes
0
Enter Zn Num.
(00 = Quit)
00
Zone Type (ZT): Each zone must be assigned to a zone type, which
defines the way in which the system responds to faults in that zone.
Enter the zone type code (or change it, if necessary). Zone types are
listed below.
00 = Not Used
06 = 24 Hr Silent
07 = 24 Hr Audible
08 = 24 Hr Aux
09 = Fire W/verification.
Default values for zones 01 to 05 are:
Zone No.(Zn):
Zone Type Default:
When the display shows the zone type you want, press [*] to advance
to...
Report Code (RC): The report code consists of 2 hexadecimal digits,
each in turn consisting of 2 numerical digits. For example, for a report
code of "3C", enter [0][3] for "3" and [1][2] for "C".
Enter the numbers and press [*] to advance to...
A summary of the programmed values for the selected zone will be
displayed.
If all is okay, press [*].
Custom Alpha Editing: For all zone types, the next request is to
enter Alpha descriptors for the zones. The entry may be done now
(enter 1), or may be done at a later time via
See Section 10. ALPHA DESCRIPTION PROGRAMMING for
procedure.
When all entries to be made for the zone at this time are complete, the
next zone number can be entered for programming, or zone
programming can be ended by entering [0][0] as the next "zone
number".
Notes:
1. In field
, at the summary line for each zone, the entered values can
*56
be checked. If it is desired to change anything, press [#] to move to
the previous entry. Press [#] a number of times to move to earlier
entries. Press [*] to move to later entries again.
2. Zone entries can be reviewed by pressing [#][5][6]. Changes cannot be
made here, so this is safer for review. Enter the first zone number to
be viewed and press [#]. To view each zone, press [#] and the zone
number will advance to the next programmed zone. When the end of
the list is reached, press [0][0] to exit. This method of exiting may
also be done at any time during the review.
–52–
16 = Fire w/
Verification
17 = Fire Waterflow
18 = Fire Supervisory
19 = 24 Hour Trouble
01
02
03
04
09
09
09
09
*82
05
09
mode (enter 0).