Bell Output; Auxiliary Relay; Built-In Indicators And Switches; Programming - ADEMCO 5110XM Installation Instructions Manual

Microprocessor-based fire alarm control/communicator
Hide thumbs Also See for 5110XM:
Table of Contents

Advertisement

Bell Output

Provides one 12VDC (nominal), 1 AMP output, which may be configured for
Style Y (for further explanation of style Y, refer to NFPA 72 National Fire
Alarm Code Chapter 3: Protected Premises Fire Alarm Systems), EOLR
supervision (for use with polarized alarm sounding devices) or for no
supervision (no EOLR used)

Auxiliary Relay

Provides a built-in 12V wet or dry (jumper selectable) "Form C" relay which can
be used for one of the following:
• Alarm activation on selected zones, silenced by Code + Off
• Trouble/Supervisory activation
• 4-wire smoke detector reset
• Battery saving feature (disconnects power from non-critical loads 4 hours
after AC power loss)
• Alarm activation on selected zones, silenced by Code + #67 (can be used for
elevator recall)

Built-in Indicators and Switches

• A built-in warning buzzer that provides alarm, supervisory, and trouble
sounds
• 7 LED indicators provide visual status of (1) AC Power, (2) Battery Trouble,
(3) Communication Failure, (4) Telco Line Fault, (5) Silenced Audible
Conditions, (6) Main Dialer Line Seize, and (7) Backup Dialer Line Seize
• A Silence/Reset push-button allows audible warnings to be silenced and
smoke detectors to be reset.

Programming

Programmed options are stored in electrically erasable, non-volatile EEROM
memory (information can be reprogrammed at any time and will not be lost
in the event of a power loss). The system can be programmed by one of the
following methods:
• Uploaded, downloaded, or controlled via an IBM compatible computer, V-
Link software and a HAYES modem specified by Ademco
• Programmed through an alpha keypad (6139, 6139R)
Remote programming may only be used when a service technician is at the site
U L
during downloading.
Keypad programming consists of:
• Data field programming
• Interactive (menu) mode programming

Communication Formats Supported

• Ademco Low Speed (Standard or Expanded)
• Sescoa/Radionics (Standard or Expanded)
• Ademco Express
• Ademco Contact ID

AC Power Input

Uses an enclosed, permanently-wired, 120VAC transformer rated @ 18.0 VAC,
40VA (supplied) with manually resettable circuit breaker.

Auxiliary Power Output

Provides 12VDC, 350 mA maximum for peripherals such as keypads. Uses
Positive Temperature Coefficient Thermistors (PTCs) for protection. There are
no replaceable fuses.
– 7–