Ademco 5110Xm Summary Of Connections - ADEMCO 5110XM Installation Instructions Manual

Microprocessor-based fire alarm control/communicator
Hide thumbs Also See for 5110XM:
Table of Contents

Advertisement

WARNING:
OWNER'S INSTRUCTION NOTICE NOT TO BE REMOVED
Refer to the 5110XM Installation Instructions N8026
for additional information
MAY BE USED AS A SLAVE DACT PROVIDING CENTRAL OR REMOTE STATION SERVICE FOR A CENTRAL
OR REMOTE STATION UL LISTED FACP. MAY ALSO BE USED AS A STAND-ALONE NON-CODED LOCAL,
CENTRAL STATION AND REMOTE STATION PROTECTED PREMISES UNIT PROVIDING MANUAL FIRE
ALARM, AUTOMATIC FIRE ALARM, SPRINKLER SUPERVISORY AND WATER FLOW ALARM. INSTALLATION
LIMITS UNDER JURISDICTION OF LOCAL AUTHORITY.
ENCLOSED TRANSFORMER
(LOWER LEFT HAND CORNER OF 5110XM CABINET
REPLACE COVER AFTER WIRING
2A CIRCUIT
BREAKER
BLUE
BLACK
120 VAC, 60Hz,
600mA MAX
CONNECT TO
BLUE
WHITE
A DEDICATED
CIRCUIT
NOTE: USE WIRES HAVING INSTALLATION
CONNECT TO
RATED FOR 90°C OR HIGHER
PROPER EARTH
GROUND. SEE
GREEN
INSTRUCTIONS
SEE AC
TRANSFORMER
– PROVIDES STYLE Y SUPERVISION
CONNECTIONS
WHEN POLARIZED ALARM
ABOVE
DEVICES ARE USED (SEE NOTE 1)
(SUPERVISED)
– RATINGS:
10-14VDC,
1A MAX,
POWER LIMITED
2K
HORN
MODEL
(SEE NOTE 2)
ALARM POLARITY SHOWN
#610-7
– AUX RELAY HAS PROGRAMMABLE FUNCTION
(NOT SUPERVISED)
– JUMPER W3 INTACT: 10-14VDC ON TERMINAL 6
350mA MAX (STANDBY)/1A MAX (ALARM),
POWER LIMITED (SEE NOTE 2). USE TERMINAL 18
FOR GROUND RETURN.
– JUMPER W3 CUT: NO VOLTAGE ON TERMINAL 6.
RELAY CONTACT RATING: 30VAC/VDC,
2A MAX, RESISTIVE LOADS
NOTES:
Note 1:
Supervision may be disabled by cutting jumper W2 and
programming zone 6 for no response.
Note 2:
The combined standby current drawn from aux power
and relay power cannot exceed 350mA.
The combined alarm current drawn from aux power,
relay power and bell cannot exceed 1.0A
Note 3:
All circuits are power limited except transformer 18VAC
output.
ALARM DEVICE MANUFACTURING CO.
A DIVISION OF PITTWAY CORPORATION
165 Eileen Way, Syosset, New York, 11791
Copyright © 1996 PITTWAY CORPORATION
N8027 4/96
5110XM SUMMARY OF CONNECTIONS
WARNING:
THIS UNIT MAY BE PROGRAMMED TO INCLUDE AN ALARM
VERIFICATION FEATURE THAT WILL RESULT IN A DELAY
OF THE SYSTEM ALARM SIGNAL FROM THE INDICATED
FIRE CIRCUITS. THE TOTAL DELAY (CONTROL UNIT PLUS
SMOKE DETECTORS) SHALL NOT EXCEED 60 SECONDS.
NO OTHER DEVICES SHALL BE CONNECTED TO THESE
CIRCUITS UNLESS APPROVED BY THE LOCAL AUTHORITY
HAVING JURISDICTION.
CIRCUIT
CONTROL UNIT
18VAC, 40VA NOT
(ZONE)
DELAY - SEC
POWER LIMITED.
CONNECT TO
AC POWER
}
TERMINALS 1, 2
MAINTAIN 1/4"
SPACING TO OTHER
WIRING.
GREEN
CONNECT TO EARTH
THE DELAY TIME MARKED ON THE INSTALLED
GROUND TERMINAL 8
DETECTORS IS TO BE USED
BLUE
AC
BLUE
AC
W2
(WHITE)
BELL+
BELL CIRCUIT SUPERVISION JUMPER
INTACT: SUPERVISED USING 2K EOLR
BELL
CUT: NOT SUPERVISED (NO EOLR USED)
BELL-
N.O.
POLE/RELAY +
AUXILIARY
RELAY
N.C.
W3
GREEN
(RED)
EARTH
GROUND
SEE
EARTH GROUND
CONNECTIONS
ABOVE
BATT –
BATT +
USE BATTERY CABLES
SUPPLIED
MAKE CONNECTIONS TO SEPARATE TELEPHONE
LINES USING CABLES SUPPLIED. SUPERVISION
12V LEAD ACID BATTERY
7AH MIN/14 AH MAX.
SEE INSTRUCTIONS FOR
WARNING: TO PREVENT RISK OF ELECTRICAL
REQUIRED CAPACITY AND
BATTERY MOUNTING
FLOAT CHARGING
CONNECTION OF THE FIRE ALARM SIGNAL TO A
VOLTAGE: 13.7V
MAXIMUM CHARGING
CURRENT: 1.0A
BATTERY NORMALLY NEED
NOT BE REPLACED FOR AT
LEAST 3 YEARS

Ademco 5110XM SUMMARY OF CONNECTIONS

THIS EQUIPMENT SHOULD BE INSTALLED IN ACCORDANCE WITH THE NATIONAL FIRE
PROTECTION ASSOCIATION'S STANDARD 72 (NATIONAL FIRE PROTECTION ASSOC.,
BATTERY MARCH PARK, QUINCY, MA 02269). PRINTED INFORMATION DESCRIBING
PROPER INSTALLATION, OPERATION, TESTING, MAINTENANCE, AND REPAIR SERVICE IS
PROVIDED WITH THIS EQUIPMENT.
LED INDICATOR BOARD
SMOKE DETECTORS
HEADER AS SHOWN
MODEL
DELAY - SEC
AC POWER
BATT TROUBLE
COMM FAIL
LINE FAULT
BACK-UP
DIALER
LINE
SEIZE
(GREEN)
RELAY POWER
COMPLIES WITH FCC RULES, PART 68
JUMPER
FCC REG. NO: AC398U-68192-AL-E
RINGER EQUIVALENCE: 0.7B
RJ31X
RJ31X
BACK-UP DIALER
MAIN DIALER
PHONE JACK
PHONE JACK
IS PROGRAMMABLE
SHOCK, DISCONNECT TELCO JACK
BEFORE SERVICING THIS PANEL
FIRE ALARM HEADQUARTERS OR A CENTRAL
STATION SHALL BE PERMITTED ONLY WITH
THE APPROVAL OF THE LOCAL AUTHORITY
HAVING JURISDICTION.
– 75–
BUZZER SILENCE SWITCH
PUSH ONCE TO SILENCE,
PUSH AGAIN TO RESET
PLUG BOARD
INTO THE J5 9 PIN
(GREEN)
J5
(YELLOW)
(YELLOW)
(YELLOW)
SILENCED
DATA OUT
(YELLOW)
DATA IN
GROUND
AUX. POWER +
ZONE 5 –
ZONE 5 +
ZONE 4 +
MAIN
ZONE 3/ZONE 4 -
DIALER
LINE
SEIZE
ZONE 3 +
(GREEN)
ZONE 2 +
ZONE 1/ZONE 2 –
ZONE 1+
ZONE 1-5 NOTES:
• ALL ZONES PROVIDE STYLE B SUPERVISION
• ZONE RESISTANCE (EXCLUDING EOLR)
+ ZONES 1-4: 300 OHM MAX
+ ZONE 5: 100 OHMS MAX
• ZONE RESPONSE: 300-500 MILLISECOND
(ALL ZONES)
• ZONE 5 RATINGS: + 10-14VDC
+ 2 MA MAX FOR 2-WIRE SMOKE
DETECTORS. UP TO 16 DETECTORS OF TYPE
SPECIFIED IN INSTRUCTIONS MAY BE USED.
+ UL COMPATIBILITY ID: A
• 2K EOLR IS ADEMCO MODEL 610-7
WARNING BUZZER
ACTIVATES ON ALARMS,
SUPERVISORIES AND TROUBLES
– AUX POWER RATING: 10-14VDC,
350mA MAX, POWER LIMITED
NOT SUPERVISED UL
(SEE NOTE 2)
– 6137, 6137R, 6139 OR 6139R MAY
BE USED AS A REMOTE KEYPAD,
KEYPAD COLOR SUBJECT TO
APPROVAL OF LOCAL AUTHORITY.
ONLY 6139 OR 6139R MAY BE USED
TO PROGRAM PANEL
– REFER TO INSTRUCTIONS FOR
MAX # OF KEYPADS AND WIRE
LENGTH RESTRICTIONS.
KEYPAD CONNECTION NOT
SUPERVISED
YELLOW
REMOTE KEYPAD.
OPTIONAL FOR
GREEN
SLAVE DACT
INSTALLATIONS.
REQUIRED FOR
BLACK
STAND ALONE
CONTROL
CONTROL
RED
INSTALLATIONS.
2K
SMOKE
N.O.
N.C.
2-WIRE SMOKE DETECTOR LOOP
N.C.
2K
N.O.
2K
N.O.
N.C.
2K
N.C.
N.O.
2K
N.O.
N.C.