Sounder Connections

Make connections to alarm output terminals 3 (+) and 4(-) (see Figure 6).
To supervise the bell wiring, do the following:
Connect polarized 12V alarm indicating devices to the bell output
terminals.
Attach a 2K EOLR (model #610-7, supplied) across the bell wires at the
last device on wire run.
Program zone 6 for 24 hour trouble response (default setting).
When supervision is not desired, do the following:
Cut the white jumper labeled W2 on control PC board.
Program zone 6 for a "0" response type (not used).

Programming for External Sounders

1. With at least one alpha keypad (6139 or 6139R) connected to the keypad
terminals on the control, power up the system temporarily.
2. Enter the programming mode by keying the following on the alpha keypad:
Master code (5 1 1 0) + 8 0
3. Press *30 (Alarm Bell Timeout)
Enter [0] for NO TIMEOUT (default) [1] for 4 mins, [2] for 8 mins, [3] for 12
mins, or [4] for 16 mins When used, the bell must be programmed to ring at
least 5 minutes.
4. Press *76 (Waterflow Alarm Silencing)
Enter [0] for MANUAL SILENCE only (default) or [1] for AUTOMATIC
SILENCE when waterflow ceases (provided no other fire alarm is present).
Note: the automatic silence option may only be used with the permission of
the local AHJ.
5. Press *77 (Alarm Bell Sound)
Enter [1] for Steady, [0] for Pulsing (default).
Note: The pulsing option causes bells to sound using NFPA three pulse
temporal pattern.
6. Press *85 (Zones 1-7 Bell / Aux. Relay Activation)
Enter [0] for NO ALARM ACTIVATION, [1] for BELL only, [2] for AUX.
RELAY only, or [3] for BELL & AUX. RELAY. (default = [1] [1] [1] [1] [1] [0]
[0] )
+