Programming the Auxiliary Relay

The auxiliary relay may be programmed for one of the following options:
• Trouble/Supervisory Activation
• Alarm Activation, silenced by [user code] + OFF
• 4-Wire Smoke Detector Reset
• Battery Saver
• Alarm Activation, silenced by [user code] + # 67
These options are described below:
• Trouble/Supervisory Activation (*34 = 0) : Steady activation in response
to any zone or system related trouble condition or to any fire supervisory
condition. Remains activated until all fault conditions have been corrected
and the Silence/Reset button has been pressed or the user code + OFF has
been entered.
• Alarm Activation, silenced by [user code] + OFF (*34 = 1): Steady
activation in response to an alarm on one, some or all zones, as selected in
fields *85 and *86. If selected, the auxiliary relay remains activated until
Aux. Relay Timeout (*31) or until the Silence/Reset button has been pressed
or until the User Code + OFF has been entered.
• 4-Wire Smoke Detector Reset (*34 = 2): Momentary (6 second) activation
at second entry of user code + OFF sequence which interrupts power to 4-
wire smoke detectors connected to hard-wired zones (zones 1-5), allowing the
detectors to be reset following an alarm. Power to 4-wire smoke detectors
should be wired to the auxiliary relay as shown above.
• Battery Saver Option (*34 = 3): When this function is selected, the
auxiliary relay will normally be activated (i.e. N.O. and pole contacts will be
connected, N.C. contact will be open) and will de-activate 4 hours after the
start of an AC power failure. Using this feature, non-critical loads (such as
supplementary keypads) which do not need to be supported for the full 24
hour battery backup period can be disconnected from the auxiliary outputs,
allowing a smaller capacity battery to be used. The relay re-activates within
a few seconds after AC power restores.
• Alarm Activation, silenced by [user code] + #67 (*34 = 4): Steady
activation in response to an alarm on one, some or all zones, as selected in
fields *85 and *86. If selected, the auxiliary relay remains activated until
the User Code + #67 has been entered.
When this function is used, the auxiliary relay can be used for elevator recall
or ventilator shutdown on fire alarms.
– 28 –