ADEMCO 5110XM Installation Instructions Manual page 41

Microprocessor-based fire alarm control/communicator
Hide thumbs Also See for 5110XM:
Table of Contents

Advertisement

The following describes each format in greater detail.
3+1 and 4+1 Standard Formats
3+1 and 4+1 Expanded Formats
4+2 Format
Ademco Contact ID
Reporting Format
Comprise a 3- (or 4-) digit subscriber number and a single digit
report code (e.g. Alarm, Trouble, Restore, etc.).
Comprise a 3- (or 4-) digit subscriber number, and a two-digit re-
port code. The first digit is displayed on the first line, followed by
a second line where the first digit is repeated 3 (or 4) times and
followed by the second digit. This is the "expanded" digit.
Comprises a 4-digit subscriber number and 2-digit report code.
Comprises a 4-digit subscriber number, 1-digit event qualifier
("new" or "restore"), 3-digit event code, and 3-digit zone number, or
sys tem status number (see the following page).
3+1/4+1
Report
Standard
Alarm
SSS(S) A
Trouble
SSS(S) T
Supervisory
SSS(S) S P
Bypass
SSS(S) B
AC Loss
SSS(S) E
Low Batt
SSS(S) L
Test
SSS(S) G
Test (Off-normal)
SSS(S) G O
Walk Test Start
SSS(S) W S
Walk Test End
SSS(S) W E
Alarm
SSS(S) R
Restore
Supervisory Restore
SSS(S) R S
AC Restore
SSS(S) R A
LoBat Res.
SSS(S) R L
Trouble Res.
SSS(S) R T
Bypass Res.
SSS(S) R B
– 41 –
3+1/4+1
Expanded
4+2
SSS(S) A
SSSS AZ
AAA(A) Z
SSS(S) T
SSSS Tt
TTT(T) t
SSS(S) S P
SSSS S P S P2
S P S P S P( S P) S P2
SSS(S) B
SSSS Bb
BBB(B) b
SSS(S) E
SSSS EA C
EEE(E) A C
SSS(S) L
SSSS LL B
LLL(L) L B
SSS(S) G
SSSS Gg
GGG(G)g
SSS(S) G O
SSSS G O G O2
G O G O G O( G O) G O2
SSS(S) W S
SSSS W S W S2
W S W S W S( W S) W S2
SSS(S) W E
SSSS W E W E2
W E W E W E( W E) W E2
SSS(S) R
SSSS RZ
RRR(R) Z
SSS(S) R S
SSSS R S R S2
R S R S R S ( R S) R S2
SSS(S) R A
SSSSR A A c
R A R A R A (R A )A c
SSS(S) R L
SSSS R L L B
R L R L R L (R L )L B
SSS(S) R T
SSSS R T t
R T R T R T (R T )t
SSS(S) R B
SSSS R B b
R B R B R B (R B )b