ADEMCO 5110XM Installation Instructions Manual page 48

Microprocessor-based fire alarm control/communicator
Hide thumbs Also See for 5110XM:
Table of Contents

Advertisement

Type 17
Fire Waterflow Alarm
Type 18
Fire Sprinkler
Supervisory
Type 19
24-Hr. Trouble
• Provides a fire alarm when zone is shorted for longer than the time
programmed in field *78 delay time setting. The combined sensor and
program field *78 delay must not exceed 90 seconds.
• Provides either a trouble on an open circuit (field *32=0) or a supervisory
on open circuit (field *32=1).
• Usually assigned to a zone containing a fire sprinkler waterflow sensor.
• Bell output may be programmed to remain latched on alarm or to restore
when zone restores (see field *76).
• Provides a supervisory indication when a zone is shorted for longer than
the time programmed in field *78 delay time setting when delay is enabled
in field *57 . The combined sensor and program field *78 delay must not
exceed 90 seconds.
• Provides either a trouble on an open circuit (field *32=0) or a supervisory
on an open circuit (field *32=1).
• No bell output is is provided.
• Usually assigned to a zone containing fire sprinkler supervisory sensors
such as Post-Indicator-Value sensors.
• Assigned to a zone that is wired to a FACP supervisory contact
• Provides a trouble response on an open or short circuit, and on system zone
faults.
• Usually assigned to system zones such as Zone 10 (earth ground fault) and
Zone 11 (main dialer fault).
• Assigned to a zone that is wired to a FACP trouble contact
–48–