Remote Programming Information - ADEMCO 5110XM Installation Instructions Manual

Microprocessor-based fire alarm control/communicator
Hide thumbs Also See for 5110XM:
Table of Contents

Advertisement

Central Station Initiated:
1. Enter program mode by entering Master code (5110) + 8 0.
2. Program the download phone number in field *94.
3. Program the ring detect count to "4" in field *95. The central station can
change this as required when on-line with the control.
4. Initialize the download ID and subscriber account number by entering *96.
5. Exit program mode by entering *98 (prevents re-entry using Master code) or
*99 (allows re-entry using Master code).
6. Wait approx. 1 minute for system to stabilize. Then the central station can
initiate the downloading session by calling the control.

Remote Programming Information

The downloading system can perform many functions while in contact with the
control. Besides uploading and downloading, the status of the system can be ob-
served and various commands can be initiated, as follows:
- Silence alarms, troubles, etc.
- Bypass a zone.
- Force the system to accept a new program download.
- Shut down communication (dialer) functions (non-payment of monitoring
fees in an owned system).
- Inhibit local keypad programming (prevents account takeover).
- Command the dialer to upload a copy of its resident program to the office.
- Read: AC power satus, lists of faulted zones, bypassed zones, zones currently
in alarm, and zones currently in trouble.
After the control and the PC have established valid communication, each
keypad on the system will become inactive and will display "CC" or "MODEM
COMM." The keypads will become active after the download communication is
terminated. The detailed operation of the download functions is covered in the
installation instructions for the V-LINK® downloading software diskette.
Remote Programming Advisory Notes
- The Control does not scan zones for fault conditions and ignores keypad
functions during the time interval stated above.
- A copy of the program downloaded may be produced from the IBM PC
compat ible computer, using the product's internal report generator, when an
optional printer is connected (consult your PC manual for proper printer and
connections).
- Program upload time - one minute, thirty seconds for a complete program.
- Program download time - depends on changes. Two minutes forty seconds
for complete program.