KEYPAD CONNECTOR CABLE
(supplied with keypads)
YELLOW
20
GREEN
19
BLACK
18
RED
17
Control
Terminals
Figure 3: Keypad Connections To The Control Board

Mounting the Keypads

1. Make sure addressable type keypads (6137, 6137R, 6139, and 6139R)
are set to the non-addressable mode (address 31), which is the factory
default setting. Refer to the instructions provided with the keypad for
address setting procedure.
2. Mount the keypads at a height that is convenient for the user. Refer to
the instructions provided with the keypad for mounting procedure.
You can either surface mount or flush mount the 6139/6139R keypads
using an appropriate Trim Ring Kit: 6139TRK - 6137/6137R keypads may
NOT be flush mounted). Refer to the mounting instructions and template
included with the keypad and/or trim ring kit for specific information.

Preliminary Check-out Procedure

If you want to check that the system is working before connecting field wiring
from zones and devices, do the following:
1. Temporarily connect a 2000 ohm end-of-line resistor across each of the hard-
wire zones 1–5, as shown in the Summary of Connections diagram.
Without actual zone wiring or EOL resistors connected, the keypads in the
system will not display the "SYSTEM NORMAL" message.
2. Power up the system temporarily.
3. B u s y – S tan d by (Alpha keypads) or Not Ready (Fixed-word keypads)
will be displayed.
After approximately 1 minute*, the built-in green AC Power indicator
should light, and the word AC (6137 or 6137R), or "SYSTEM NORMAL"
(6139 or 6139R) should be displayed. * To bypass the 1-minute delay, press
# plus 0.
If keypads appear to be "dead" and are inoperable check that the keypads'
address is set to "31" as described in the instructions provided with the
keypad for address setting procedure.
If the "AC" or "SYSTEM NORMAL" display does not appear on any of the
keypads in the system or a Zone Fault message is displayed, make sure each
of the 5 basic hard-wired zones has a 2000 ohm resistor connected across its
terminals.
4. When you get the proper "AC" or "SYSTEM NORMAL" message displayed
on the keypad(s), the system is functioning properly at this point.
Do not remove the EOL resistors until you are ready to make connections to
the hard-wired zones, to allow for testing later in the manual.
If an OC or OPEN CIRCUIT is present on the keypad, data from the control is
not reaching the keypad. Please check the wiring (yellow data lead).
KEYPAD
– 14–