Section 4. MECHANICS OF PROGRAMMING

This section provides the following information:
• How to enter and exit the programming mode
• How to program a data field
• How to review an entry in a data field
• How to erase an entry in a data field
• How to program user-friendly interactive modes ( * 56, * 82)
• Loading factory defaults
General Programming Information
Characteristics for each installation are stored in non-removable, electrically
erasable, non-volatile EEROM memory. These must be programmed for the
particular installation to establish its specific alarm and reporting features.
It is possible to program the system at any time, even at the installer's
premises prior to the actual installation. Simply apply power temporarily to
the control and then program the unit as desired.
There are two programming modes: data field programming and interactive
(menu) mode programming. Data field programming is used for setting various
system options and interactive programming is used for programming zone
information.
To program the system, you must use a 6139 or 6139R Alpha keypad
connected to keypad terminals on the control (17, 18, 19, and 20). The Alpha
keypad need not necessarily remain in the system after programming.
Programming can also be performed remotely from the installer's office/home,
using an IBM (or compatible) personal computer (or laptop), a Hayes modem,
and V-Link downloading software. See the REMOTE PROGRAMMING AND
CONTROL (DOWNLOADING) section for details.

Entering Program Mode

You may use one of the following methods:
a) Press both the [
power is applied to the control, or
b) After power up, enter the Master code (5 1 1 0) + 8 0
This method is disabled if you exit the program mode using
99. See "Exiting Program Mode" paragraph later in this section.
*
If a different Master code is subsequently programmed, use it instead of
5110 to gain access to the programming mode.
Following entry into program mode, the built-in indicators will simultaneously
flash and the alpha keypad will display field *20 (this is the first field in the
system). The system will now accept entries for field
Before programming data fields for the first time, enter *97 to load
factory defaults! Then press *96 if downloading is to be performed.

Programming a Data Field

1. Press [
2. When you have completely programmed a data field, the keypad will "beep"
three times and then automatically display the next data field in sequence.
To go to a different field, press [
3. If the number of digits that you need to enter in a data field is less than the
maximum digits available (for example, the phone number field), enter the
] and [#] keys at the same time within 50 seconds after
*
] plus Field No. (for example,
*
– 15–
*
20.
), then make the required entry.
*20
] plus the desired field no..
*
98 instead of
*