Section 1. GENERAL DESCRIPTION

The Ademco 5110XM is a UL Listed, microprocessor-based fire alarm
control/communicator that supports 5 style B (for further explanation of
style B, refer to NFPA 72 National Fire Alarm Code Chapter 3: Protected
Premises Fire Alarm Systems) hardwired zones. It may be used as a slave
Digitial Alarm Communicator Transmitter (DACT) providing central or
remote station service for a central or remote station listed Fire Alarm
Control Panel (FACP). It may also be used as a standalone non-coded local,
central station or remote station control.
Basic Hardwired Zones
Provides 5 style B hardwired zones having the following characteristics:
• EOLR supervision supporting
detectors, water flow switches, etc. or N.O./N.C. contacts from a listed fire
alarm control panel
• 300 – 500ms response time
• Individually assignable to bell output and/or aux. relay
• Supports up to 16 2-wire smoke detectors on Zone 5
• Supports 4-wire smoke detectors on any zone (power to these should be
supplied from the control's auxiliary relay power output; see the section
on Hardwired Zones)
• Tolerance of 300-ohm resistance on zones 1-4, 100-ohm resistance on zone
5 (excluding EOLR)

Remote Keypads

• When used as a DACT only, a keypad is not required, but may be used to
provide supplementary status annunciation.
• When used as a control, a keypad must be used.
The following keypads may be used:
Fixed-Word Keypads: 6137 (gray) or 6137R (red)
A 6139 or 6139R keypad must be used for keypad programming.
User Codes (for use with remote keypads)
• 1 Master code for entire system (user 1– intended for use by installer)
• 5 secondary user codes (users 2–6; user 2 intended for use by principle
end user)

Keypad Emergency Keys

Provides up to 3 programmable emergency key functions:
• Designated as Zones 7, 95, and 96
• Can be programmed for 24-hr. silent, audible, auxiliary, or fire responses
• Intended to be used only when the 5110XM is installed as a stand alone
control.

Backup Dialer

Has built-in backup dialer for connecting to a second supervised telephone line.
Alpha Keypads: 6139 (gray) or 6139R (red)
– 6–
N.O./N.C. sensors such as smoke