Connecting The Power Supply; Fig. 17: Connecting The Power Supply For Base Devices - Eaton easyE4 Manual

Hide thumbs Also See for easyE4:
Table of Contents

Advertisement

2. Installation
2.4 Connection terminals

2.4.3 Connecting the power supply

68
Cable protection
NOTICE
Make sure to meet all relevant line protection requirements!
Connect a circuit protection device (F1) rated for at least 1 A (slow) to all base
devices.
You may need a higher circuit protection rating depending on the type and con-
nection of the expansion devices (F1).
You can use a shared, adequately sized circuit protection device for the base device,
expansion device(s), and easy communication module that takes into account the
amount - a maximum of 11 and the terminal - with UC, DC, and AC power.
AC:
L
100 - 240 V AC/DC (cULus 100 - 110 V DC)
Ue
UC:
12, 24 V DC/24 V AC
DC:
24 V DC
0 V/ N
F1 > 1 A
+24 V 0 V

Fig. 17: Connecting the power supply for base devices

easyE4  02/24 MN050009EN  Eaton.com
+ UC 0 V
L N N