Application Set-up Examples

6 Application Set-up Examples
The examples in this section are intended as a quick
reference for common applications.
Parameter settings are the regional default values
unless otherwise indicated (selected in
parameter 0-03 Regional Settings).
Parameters associated with the terminals and
their settings are shown next to the drawings.
Required switch settings for analog terminals A53
or A54 are also shown.
NOTICE!
When using the optional STO feature, a jumper wire may
be required between terminal 12 (or 13) and terminal 37
for the frequency converter to operate with factory
default programming values.
6.1 Application Examples
6.1.1 Feedback
FC
+24 V
12
13
+24 V
18
D IN
D IN
19
COM
20
D IN
27
29
D IN
32
D IN
D IN
33
D IN
37
+10 V
50
+
A IN
53
A IN
54
-
4-20 mA
COM
55
A OUT
42
COM
39
U - I
A 54
Table 6.1 Analog Current Feedback Transducer
MG20MC22
Operating Instructions
Parameters
Function
Setting
Parameter 6-22
4 mA*
Terminal 54
Low Current
Parameter 6-23
20 mA*
Terminal 54
High Current
Parameter 6-24
0*
Terminal 54
Low Ref./Feedb.
Value
Parameter 6-25
50*
Terminal 54
High Ref./
Feedb. Value
* = Default value
Notes/comments:
D IN 37 is an option.
Danfoss A/S © 01/2015 All rights reserved.
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
+
A IN
53
A IN
54
COM
55
-
A OUT
42
0 - 10V
COM
39
U - I
A54
Table 6.2 Analog Voltage Feedback Transducer (3-wire)
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
+
A IN
53
A IN
54
COM
55
A OUT
42
-
COM
39
0 - 10V
U - I
A54
Table 6.3 Analog Voltage Feedback Transducer (4-wire)
Parameters
Function
Setting
Parameter 6-20 T
0.07 V*
erminal 54 Low
Voltage
Parameter 6-21 T
10 V*
erminal 54 High
Voltage
Parameter 6-24 T
0*
erminal 54 Low
Ref./Feedb. Value
Parameter 6-25 T
50*
erminal 54 High
Ref./Feedb. Value
* = Default value
Notes/comments:
D IN 37 is an option.
Parameters
Function
Setting
Parameter 6-20 T
0.07 V*
erminal 54 Low
Voltage
Parameter 6-21 T
10 V*
erminal 54 High
Voltage
Parameter 6-24 T
0*
erminal 54 Low
Ref./Feedb. Value
Parameter 6-25 T
50*
erminal 54 High
Ref./Feedb. Value
* = Default value
Notes/comments:
D IN 37 is an option.
33