Application Set-up Examples

6 Application Set-up Examples
The examples in this section are intended as a quick
reference for common applications.
Parameter settings are the regional default values
unless otherwise indicated (selected in parameter
0-03 Regional Settings).
Parameters associated with the terminals and
their settings are shown next to the drawings.
Where switch settings for analog terminals A53 or
A54 are required, these are also shown.
NOTICE
When the optional STO feature is used, a jumper wire
may be required between terminal 12 (or 13) and
terminal 37 for the frequency converter to operate when
using factory default programming values.
6.1 Application Examples
6.1.1 AMA
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Table 6.1 AMA with T27 connected
MG33AP02
Operating Instructions
Parameters
Function
Setting
1-29 Automatic
[1] Enable
Motor
complete
Adaptation
AMA
(AMA)
5-12 Terminal 27
[2]* Coast
Digital Input
inverse
* = Default Value
Notes/comments:
Parameter group 1-2* Motor
Data must be set according to
motor
D IN 37 is an option.
Danfoss A/S © Rev. 07/2014 All rights reserved.
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Table 6.2 AMA without T27 connected
6.1.2 Speed
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
+
A IN
53
A IN
54
COM
55
-
A OUT
42
-10 - +10V
COM
39
U - I
A53
Table 6.3 Analog Speed Reference (Voltage)
Parameters
Function
Setting
1-29 Automatic
[1] Enable
Motor
complete
Adaptation
AMA
(AMA)
5-12 Terminal 27
[0] No
Digital Input
operation
* = Default Value
Notes/comments:
Parameter group 1-2* Motor
Data must be set according to
motor
D IN 37 is an option.
Parameters
Function
Setting
6-10 Terminal 53
0.07 V*
Low Voltage
6-11 Terminal 53
10 V*
High Voltage
6-14 Terminal 53
0 Hz
Low Ref./Feedb.
Value
6-15 Terminal 53
50 Hz
High Ref./Feedb.
Value
* = Default Value
Notes/comments:
D IN 37 is an option.
31
6