Option
LCD Password
Length Calibration
Factor
4-20mA Leak Alarm
Output Span
4-20mA Leak Alarm
Output Range
Preventative
Maintenance Alarm
Preventative
Maintenance LCD
Ack Code
Preventative
Maintenance Text
LCD Midnight Reset
Table 4.1
rletech.com
Description
Establish a 4-digit numerical code to access the Setup series of
menus through the LCD. Set the value to 0000 if you don't wish to
have a password.
Default setting: 0000 (no password)
Reserved for manufacturer's use only.
Selectable: 5-19mA or 4-20mA
Default setting: 5-19mA
Selectable:
1000 feet
2500 feet
5000 feet
7500 feet
10000 feet
Default setting: 1000 feet
Preventative maintenance keeps a leak detection system running
efficiently and reliably. Use this option to program a preventative
maintenance alarm reminder into the system.
Select a span of days to elapse between maintenance alarms, from
30-720 days. Set the value to 0 to disable this option.
Default setting: 0 (disabled)
Establish a 4-digit numerical code to acknowledge the preventative
maintenance alarm. Set the value to 0000 if you don't wish to have
a password.
Default setting: 0000 (no password)
Designate text to display when the maintenance reminder is
triggered.
Enter up to four lines of text (30 characters per line)
Default setting: blank
By default the unit's LCD will reset at midnight every night. In some
rare instances, this causes the device to have a momentary
connectivity failure at midnight. If a loss of connectivity is being
reported at your facility, you can disable the LCD reset.
Use this option to enable or disable the 12:00 a.m. LCD reset.
Default: Enabled
Leak Configuration Options (continued)
LD5200 User Guide
4
Web Interface
53