17. APPLICATION OF FUNCTIONS
No.
Symbol
PX28
CVAT
SEMI-F47 function - Instantaneous power failure detection time
Set the time until the occurrence of [AL. 10.1 Voltage drop in the control circuit
power].
To disable the parameter, set "Disabled (_ 0 _ _)" of "SEMI-F47 function selection"
in [Pr. PX25].
PX29
DRAT
Drive recorder arbitrary alarm trigger setting
Setting
digit
_ _ x x
x x _ _
Setting example:
To activate the drive recorder when [AL. 50 Overload 1] occurs, set "5 0 0 0".
To activate the drive recorder when [AL. 50.3 Thermal overload error 4 during
operation] occurs, set "5 0 0 3".
PX30
DRT
Drive recorder switching time setting
Set the drive recorder switching time.
When a USB communication is cut during using a graph function, the function will
be changed to the drive recorder function after the setting time of this parameter.
When a value from "1" to "32767" is set, it will switch after the setting value.
However, when "0" is set, it will switch after 600 s.
When "-1" is set, the drive recorder function is disabled.
PX31
XOP4
Function selection X-4
Setting
digit
_ _ _ x
_ _ x _
_ x _ _
x _ _ _
Name and function
Explanation
Alarm detail No. setting
Set the digits when you execute the trigger with arbitrary
alarm detail No. for the drive recorder function.
When these digits are "0 0", only the arbitrary alarm No.
setting will be enabled.
Alarm No. setting
Set the digits when you execute the trigger with arbitrary
alarm No. for the drive recorder function.
When "0 0" are set, arbitrary alarm trigger of the drive
recorder will be disabled.
Explanation
Robust filter selection
0: Disabled
1: Enabled
When you select "Enabled" of this digit, the machine
resonance suppression filter 5 set in [Pr. PX22] is not
available.
For manufacturer setting
17 - 23
Initial
Setting
value
range
[unit]
200
30
[ms]
to
200
Refer to Name and
function column.
Initial
value
00h
00h
0
-1
[s]
to
32767
Refer to Name and
function column.
Initial
value
0h
0h
0h
0h
Each/
common
Common
Common
Common
Each
axis