SMC Networks HRSH090-A Operation Manual page 88

Thermo chiller hrsh090 series
Table of Contents

Advertisement

HRX-OM-R026
Chapter 5
Display and setting of various functions
Offset temperature Setting and checking
4.
Press the [SEL] key once.
The set screen of offset temperature is displayed on the digital display.
PV
SV
5.
Select offset temperature from the table below with [▲] key or [▼] key, and confirm by
pressing "SEL".
Set value
Centigrade
to
Fahrenheit
to
 This function controls the offset temperature to the circulating fluid
discharge temperature
 Control range of the circulating fluid temperature is 5.0
(41.0
 When the circulating fluid temperature is set to 5.0
offset temperature to -20.0
automatically adjusted to 0.0
mode.
6.
Press the [MENU] key once.
Return to the main screen (screen displaying the circulating fluid temperature).
PV
SV
5.9 Offset function
5-26
Table 5.9-3
Explanation
Setting and checking are not available when
offset mode setting is OFF.
Sets offset temperature.
Temperature unit is Centigrade : Setting unit is
o
0.1
C
Temperature unit is Fahrenheit : Setting unit is
o
0.1
F
o
o
F to 104.0
F).
List of set value
(Default setting)
o
o
C (-36.0
F), the offset temperature is
o
o
C (0.0
F) depending on the offset
Initial
o
o
C to 40.0
C
o
o
C (41
F) and the
HRSH Series