SMC Networks HRSH090-A Operation Manual page 137

Thermo chiller hrsh090 series
Table of Contents

Advertisement

30.
Select contact input signal 1 from the table below with [▲] key or [▼] key, and confirm
by pressing "SEL".
Set value
4:When the setting of the communication mode is "DIO mode", "External switch signal" cannot
be set.
5:When the setting of the communication mode is "SEIRAL mode" and the protocol setting is
"Simplified communication protocol 2", "External switch signal" cannot be set.
Contact input signal 1 type Setting and checking
31.
Press the [SEL] key once.
The set screen of contact input signal 1 type is displayed on the digital display.
PV
SV
32.
Select contact input signal 1 type from the table below with [▲] key or [▼] key, and
confirm by pressing "SEL".
Set value
6:Used when the setting of the contact input 1 is "Operation stop signal input".
Contact input signal 1 delay timer of reading Setting and checking
33.
Press the [SEL] key once.
The set screen of the contact input signal 1 delay timer of reading is displayed on the
digital display.
PV
SV
HRSH Series
Table 5.21-16 List of set value
Explanation
Without signal input
Start and stop signal input
External switch signal input(N.O. type)
External switch signal input (N.C. type)
Table 5.21-17 List of set value
Explanation
Setting/checking are not available if the
setting of contact input signal 1 is OFF.
Alternate signal
 6
Momentary signal
Chapter 5
Display and setting of various functions
(Default setting)
 4,  5
 4,  5
(Default setting)
HRX-OM-R026
Initial value
Initial value
5.21Communication function
5-75