SMC Networks HRSH090-A Operation Manual page 126

Thermo chiller hrsh090 series
Table of Contents

Advertisement

HRX-OM-R026
Chapter 5
Display and setting of various functions
39.
Select the changing of circulating fluid pressure sensor failure from the table below with
[▲] key or [▼] key, and confirm by pressing "SEL".
Set value
AL06, AL07, AL08, and AL09 will be disabled when A.RUN is selected.
(AL06, AL07, AL08, and AL09 will not be generated). If operation continues
with this condition, pump failure cannot be detected. A.STP is
recommended.
Changing of pump maintenance Setting and checking
40.
Press the [SEL] key once.
The set screen of the circulating fluid pressure sensor failure is displayed on the digital
display.
PV
SV
41.
Select the changing of pump maintenance from the table below with [▲] key or [▼] key,
and confirm by pressing "SEL".
Set value
Changing of Changing of fan maintenance Setting and checking
42.
Press the [SEL] key once.
The set screen of the changing of fan maintenance is displayed on the digital display.
PV
SV
5.20 Alarm customizing function
5-64
Table 5.20-27
Explanation
Operation continues when this alarm signal is
generated.
Operation is stopped when this alarm signal is
generated.
Table 5.20-28
Explanation
This alarm signal is not detected.
Operation continues when this alarm signal is
generated.
List of set value
(Default setting)
List of set value
(Default setting)
Initial value
Initial value
HRSH Series