SMC Networks HRSH090-A Operation Manual page 122

Thermo chiller hrsh090 series
Table of Contents

Advertisement

HRX-OM-R026
Chapter 5
Display and setting of various functions
Monitoring start timer Setting and Checking
32.
Press the [SEL] key once.
Setting screen of the monitoring start timer is displayed on the digital display.
PV
SV
33.
Select monitoring start timer from the table below with [▲] key or [▼] key, and confirm
by pressing "SEL".
Set value
to
 Settings of this function and example of alarm generating timing for 5.15.3 "Setting of
temperature alarm monitoring method and generation timing".
Range over detection timer Setting and Checking
34.
Press the [SEL] key once.
Setting screen of the range over detection timer is displayed on the digital display.
PV
SV
35.
Select the time of the range over detection timer from the table below with [▲] key or
[▼] key, and confirm by pressing "SEL".
Set value
to
 Settings of this function and example of alarm generating timing for 5.15.3 "Setting of
temperature alarm monitoring method and generation timing".
5.20 Alarm customizing function
5-60
Table 5.20-23 List of set value
Explanation
Setting and checking are impossible when "0:
Continuous monitoring" or "1: Automatic
monitoring" is selected for the setting of AS21
"Temperature alarm monitoring method".
Sets the time when alarm monitoring starts
Setting unit is 1 minute.
Table 5.20-24
Explanation
Sets time from detecting the alarm to
generation of the alarm.
Setting unit is 1 second.
(Default setting)
List of set value
(Default setting)
Initial value
Initial value
HRSH Series