Changing of circulating fluid discharge pressure rise Setting and checking
12.
Press the [SEL] key once.
The set screen of changing of circulating fluid discharge pressure rise is displayed on the
digital display.
PV
SV
13.
Select changing of circulating fluid discharge pressure rise from the table below with [▲]
key or [▼] key, and confirm by pressing "SEL".
Set value
Detection pressure for circulating fluid discharge pressure rise Setting and checking
14.
Press the [SEL] key once.
The set screen of detection temperature for circulating fluid discharge pressure rise is
displayed on the digital display.
PV
SV
15.
Select detection temperature for circulating fluid discharge pressure rise from the table
below with [▲] key or [▼] key, and confirm by pressing "SEL".
Set value
MPa
to
PSI
to
HRSH Series
Table 5.20-13 List of set value
Explanation
This alarm signal is not detected.
Operation continues when this alarm signal is
generated.
Operation is stopped when this alarm signal is
generated.
Table 5.20-14 List of set value
Explanation
Setting/checking are not available if the
setting of the circulating fluid discharge
pressure rise is OFF.
Sets detection pressure for the circulating
fluid discharge pressure rise.
Pressure unit is MPa : Setting unit is
0.01MPa
Pressure unit is PSI : Setting unit is 1PSI
Chapter 5
Display and setting of various functions
(Default setting)
HRX-OM-R026
Initial value
Initial value
(Default setting)
5.20Alarm customizing function
5-55