KEB Combivert F5 series Installation Manual page 43

5.5...7.5kw 230v 4.0...15kw 400v
Hide thumbs Also See for Combivert F5 series:
Table of Contents

Advertisement

Annex B
Table for input fusing of inverters F5-A housing:
Inverter
05F5
05F5
07F5
07F5
05F5
07F5
09F5
*) The voltage rating of the Class rated fudes (CC, J or RK5) shall be at least equal to the
voltage of the Drivers.
Branch Circuit Protection: Type E Self Protected Manual Motor Controllers for
inverters F5-A housing.
Cat. No.
05F5
05F5
07F5
07F5
GB - 88
Input Voltage
[V]
240 / 1ph
240 / 1ph
240 / 1ph
240 / 1ph
400 / 480 / 3ph
400 / 480 / 3ph
400 / 480 / 3ph
Drive Input
Self Protected Manual Motor
ating
Controller Type and manufac-
240V / 1ph
PKZMO-10E, Eaton Industries
240V / 3ph
PKZMO-6.3E, Eaton Industries
240V / 3ph
PKZMO-16E, Eaton Industries
240V / 1ph
PKZMO-10E, Eaton Industries
UL 248 Fuse Class
J or RK5 *
[A]
10
6
15
10
5
6
10
turer
UL 248 Fuse Class
CC *)
[A]
10
5
20
10
---
---
---
Self Protected Manual
Motor Controller rating
230V, 1.5 hp
230V / 3ph, 1.5 hp
230V, 2 hp
230V / 3ph, 3 hp

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Combivert f5

Table of Contents