Oriented Start-Up - WEG CFW-11 User Manual

Hide thumbs Also See for CFW-11:
Table of Contents

Advertisement

5.2.2 Oriented Start-Up

There is a group of parameters named "Oriented Start-up" that makes the inverter settings easier. Inside this
group, there is a parameter P0317, that shall be set to enter into the Oriented Start-up routine.
The Oriented Start-up routine allows you to quickly set up the inverter for operation with the line and motor
used. This routine prompts you for the most commonly used parameters in a logic sequence.
In order to enter into the Oriented Start-up routine, follow the sequence presented in
first modifying parameter P0317 = 1 and then, setting the other parameters as they are displayed on the HMI.
Setting the parameters in the Oriented Start-Up routine causes the automatic content modification of the other
parameters and/or internal inverter variables.
During the Oriented Start-up routine, the message "Config" will be displayed at the left top corner of the HMI display.
Step
Action/Result
1
- Monitoring mode
- Press "Menu"
(right soft key)
3
- Group "01
PARAMETER GROUPS" is
selected
5
- Parameter "Oriented Start-
Up P0317: No" has been
already selected
- Press "Select"
7
- The parameter value is
modified to "P0317 = [001]
Yes"
- Press "Save"
Display Indication
Step
Ready
0rpm
LOC
0
rpm
0.0
A
0.0
Hz
13:48
Menu
Ready
0rpm
LOC
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
Return
13:48
Select
Ready
LOC
0rpm
Oriented Start-Up
P0317: No
Return
13:48
Select
Ready
0rpm
LOC
P0317
Oriented Start-up
[001] Yes
Return
13:48
Save
First Time Power-Up and Start-Up
Action/Result
2
- Group "00
ALL PARAMETERS" has
been already selected
4
- Group "02
ORIENTED START-UP" is
then selected
- Press "Select"
6
- The value of
"P0317 = [000] No"
is displayed
8
- At this point the Oriented
Start-up routine starts and the
"Config" status is displayed
at the top left corner of the
keypad
- The parameter "Language
P0201: English" is already
selected
- If needed, change the
language by pressing
"Select". Then, press
or
to scroll through the
available options and press
"Save" to select a different
language
Figure 5.2 on page
5-4,
Display Indication
Ready
0rpm
LOC
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
Return
13:48
Select
Ready
0rpm
LOC
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
Return
13:48
Select
Ready
LOC
0rpm
P0317
Oriented Start-up
[000] No
Return
13:48
Save
Config
0rpm
LOC
Language
P0201: English
Type of Control
P0202: V/F 60 HZ
Reset
13:48
Select
CFW-11 | 5-3
5

Hide quick links:

Advertisement

Table of Contents
loading