Fault/Alarm
A704
(4)
Two movements have been enabled.
Two Movements
Enabled
A706
Speed reference not programmed for SoftPLC .
(4)
Speed Reference
Not Programmed for
SoftPLC
(1) Very long motor cables (longer than 100 meters) present a high parasite capacitance against the ground. The circulation of parasite currents
through those capacitances may cause the ground fault circuit activation and thus disabling the inverter with F074, immediately after the inverter
enabling. Possible solutions:
- Decrease the carrier frequency (P0297).
- Install an output reactor between the inverter and the motor.
(2) With a Profibus DB module connected into the slot 3 (XC43).
(3) With IOE-01 (02 or 03) modules connected into the slot 1 (XC41).
(4) All the models with a SoftPLC applicative.
Description
Troubleshooting and Maintenance
Possible Causes
It occurs when two or more movement blocks are enabled
simultaneously.
It occurs when a movement block has been enabled and the
speed reference has not been configured for SoftPLC (check
P0221 and P0222).