5.2.2 Oriented Start-Up

There is a group of parameters named "Oriented Start-up", which makes the inverter settings easier. The
parameter P0317 from this group allows entering the Oriented Start-up routine.
The Oriented Start-Up routine presents the main parameters on the HMI in a logical sequence, so that their
setting, according to the operation conditions, prepares the inverter for the operation with the used line and motor.
In order to enter into the Oriented Start-up routine, follow the steps presented in figure 5.2, first changing
parameter P0317 to 1 and then, setting all remaining parameters as they are presented on the display.
Setting the parameters in the Oriented Start-Up routine causes the automatic content modification of the other
parameters and/or internal inverter variables.
During the Oriented Start-up routine, the message "Config" will be displayed at the top left corner of the HMI
display.
Step
Action/Result
- Monitoring Mode.
1
- Press "Menu"
(right soft key).
- The group "00 ALL
PARAMETERS" is already
2
selected.
- The group "01
PARAMETER GROUPS" is
3
selected.
- The group "02
ORIENTED START-UP" is
4
then selected.
- Press "Select".
- The parameter
"Oriented Start-up
5
P0317: No" is already
selected.
- Press "Select".
- The content of "P0317
6
= [000] No" is showed.
Display indication
Ready
0rpm
LOC
0
rpm
0.0
A
0.0
Hz
13:48
Menu
Ready
LOC
0rpm
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
Return
13:48
Select
Ready
0rpm
LOC
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
Return
13:48
Select
Ready
0rpm
LOC
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
Return
13:48
Select
Ready
0rpm
LOC
Oriented Start-Up
P0317: No
Return
13:48
Select
Ready
0rpm
LOC
P0317
Oriented Start-up
[000] No
Return
13:48
Save
Figure 5.2 - Oriented Start-up
First Time Power-Up and Start-Up
Step
Action/Result
- The content of the
parameter is changed to
7
"P0317 = [001] Yes".
- Press "Save".
- At that moment the
Oriented Start-up
routine is initiated and
the "Config" status is
indicated at the top left
corner of the HMI.
- The parameter
"Language P0201:
English" is already
8
selected.
- If necessary, change
the language by pressing
"Select", next
and
to select the
language and then press
"Save".
- If necessary, change the
value of P0202 according
to the type of control. To
do so, press "Select".
- The settings listed
here are valid only for
P0202=0 (V/f 60 Hz) or
9
P0202=1 (V/f 50 Hz). For
other options (Adjustable
V/f, V V W, or Vector
modes), please refer to
the programming manual.
Display indication
Ready
0rpm
LOC
P0317
Oriented Start-up
[001] Yes
Return
13:48
Save
Config
0rpm
LOC
Language
P0201: English
Type of Control
P0202: V/F 60 HZ
Reset
13:48
Select
Config
0rpm
LOC
Language
P0201: English
Type of Control
P0202: V/F 60 HZ
Reset
13:48
Select
5-3