3.2.6 Typical Control Connections

Control connection 1 - Run/Stop function controlled from the keypad (Local Mode).
With this control connection it is possible to run the inverter in local mode with the factory default settings. This
operation mode is recommended for first-time users, since no additional control connections are required.
For the start-up in this operation mode, please follow instructions listed in
AND START-UP on page
Control connection 2 - 2 - Wire Start/Stop function (Remote Mode).
This wiring example is valid only for the default factory settings and if the inverter is set to remote mode.
With the factory default settings, the selection of the operation mode (local/remote) is performed through the
operator key
LOC
(local mode is default). Set P0220 = 3 to change the default setting of HMI key
REM
remote mode.
H
≥5 kΩ
AH
Run/Stop
Forward/Reverse
(FWD/REV)
Jog
5-1.
Connector XC1
1
+ REF
2
AI1+
3
AI1-
4
- REF
5
AI2+
6
AI2-
7
AO1
8
AGND (24 V)
9
AO2
10
AGND (24 V)
11
DGND *
12
COM
13
24 Vcc
14
COM
15
DI1
16
DI2
17
DI3
18
DI4
19
DI5
20
DI6
21
NF1
DO1
22
C1
(RL1)
23
NA1
24
NF2
DO2
25
C2
(RL2)
26
NA2
27
NF3
DO3
28
C3
(RL3)
29
NA3
Figure 3.24 - XC1 wiring for control connection #2
Installation and Connection
Chapter 5 FIRST TIME POWER-UP
CFW-11 | 3-31
LOC
to
REM
3