Operating Guide
6.7 T sensor defect
MENU > Event > T sensor defect
Event priority 1
Circuit
All
The event number and priority possibilities.
The event can be activated if a monitored* temperature sensor should be
disconnected, short-circuited or the sensor itself be defective.
* See Appendix "Parameter ID overview"
0:
Log of event not active
1:
Log of event in list
2:
Log of event in list and notice (letter symbol in display)
3:
Log of event in list and alarm (bell symbol in display and
activation of alarm output)
* Monitoring the temperature sensors:
In the "Raw input overview" (MENU > Common controller settings
> System > Raw input overview) the sensor(s) in question is /
are marked (dial-click) by means of the cursor. A symbol for a
magnifying glass appears.
The temperature sensor(s) is / are now being monitored.
Should the connection to the temperature sensor be disconnected,
short-circuited or the sensor itself is defective, the event function is
activated.
Resetting the event:
Go to "Raw input overview" (MENU > Common controller settings
> System > Raw input overview). See the sensor marked with a
bell-symbol (alarm).
Mark the line by means of the cursor and click the dial. The symbols
for alarm and magnifying glass disappears.
When the dial is pressed again, the monitoring function is
reactivated.
When the event priority is set to "2", the bell-symbol is not shown.