Operating Guide

5.6 Flow meter

(P318.10)
A flow meter, F1, measures the Cold Water flow to the
heat-exchanger. The signal form is pulses. The pulses are applied
to "Pulse in 1" on the ECA 32 / 35 module.
The water flow can be displayed in l / h (liters / hour) or m3 / h
(cubic meters / hour).
Parameters indicated with an ID no. like "1x607" mean a universal
parameter.
x stands for circuit / parameter group.
MENU > Settings > Flow meter
Actual
Circuit
1
Actual cold water flow.
The value is based on the setting "Pulse" (1x114) and applied pulse signal.
MENU > Settings > Flow meter
Pulse
Circuit
1
Assigning the value of each pulse from the flow meter. The setting
determines the read-out value in "Actual".
An example: Value 20 means that each pulse represents 20 liters.
1 - 9999:
Value of each pulse.
MENU > Settings > Flow meter
Units
Circuit
1
Setting desired unit for the read-out of actual flow.
Danfoss District Energy
ECL Comfort 310, application P318
Setting range
Factory setting
*
1x114
Setting range
Factory setting
*
1x115
Setting range
Factory setting
*
*
*
*
VI.JM.Q3.02