Operating Guide
MENU > Settings > Boiler
MENU > Settings > Control par.
MENU > Settings > Control par., cool.
MENU > Settings > Control par., fan
MENU > Settings > Control par., inlet
MENU > Settings > Control par., outlet
MENU > Settings > Control par. 1
MENU > Settings > Control par. 2
MENU > Settings > Control par. 3
MENU > Settings > Control par., P circ.
MENU > Settings > Control par., P refill
Xp (proportional band)
Circuit
All
* See Appendix "Parameter ID overview"
Set the proportional band. A higher value will result in a stable but
slow control of the flow / duct temperature.
Special for the parameters 11184 / 12184 / 13184:
Set the proportional band for the speed control. A higher value will
result in a stable, but slow control of the speed.
MENU > Settings > Boiler
MENU > Settings > Control par.
MENU > Settings > Control par., cool.
MENU > Settings > Control par., fan
MENU > Settings > Control par., inlet
MENU > Settings > Control par., outlet
MENU > Settings > Control par. 1
MENU > Settings > Control par. 2
MENU > Settings > Control par. 3
MENU > Settings > Control par., P circ.
MENU > Settings > Control par., P refill
Tn (integration time constant)
Circuit
All
* See Appendix "Parameter ID overview"
Set a high integration time constant (in seconds) to obtain a slow
but stable reaction to deviations.
A low integration time constant will make the controller react fast
but with less stability.
Special for 11184 / 12184 / 13184:
Set the integration time for the speed control. Set a higher value
(in seconds) to obtain a slow, but stable reaction to deviations.
A low integration time constant will make the controller react fast,
but with less stability.
70
DEN-SMT/DK
ECL Comfort 310, application P318
1x184
Setting range
Factory setting
*
1x185
Setting range
Factory setting
*
*
*
VI.JM.Q3.02
Danfoss District Energy