Operating Guide
Parameters indicated with an ID no. like "1x607" mean a universal
parameter.
x stands for circuit / parameter group.
MENU > Event > Tank temperature
Event priority 41
Circuit
All
The event number and priority possibilities.
The event can be activated if the tank temperature S6 has been too low for
more than the set "Delay" time.
* See Appendix "Parameter ID overview"
0:
Log of event not active
1:
Log of event in list
2:
Log of event in list and notice (letter symbol in display)
3:
Log of event in list and alarm (bell symbol in display and
activation of alarm output)
MENU > Event > Charge T
MENU > Event > Tank temperature
MENU > Event > DHW flow T
MENU > Event > Supply T
Delay
Circuit
All
If an event from either 'Upper difference' or 'Lower difference' is present for a
longer time than the set delay (in minutes), the event is registered.
* See Appendix "Parameter ID overview"
Value:
The event will be present if the alarm condition remains
after the set delay.
88
DEN-SMT/DK
ECL Comfort 310, application P318
9041
Setting range
Factory setting
*
1x149
Setting range
Factory setting
*
*
Delay, example
Y
*
=
X
Time
=
Y
Temperature
=
# 1 #
Lower difference
=
# 2 #
Desired temperature
=
# 3 #
Actual temperature
=
# 4 #
Delay (ID 1x149)
VI.JM.Q3.02
#
1 #
# 2 #
# 3 #
#
4 #