Operating Guide
MENU > Settings > Tank temperature
Max. charge T (maximum heating / charging temperature)
Circuit
All
Set the max. heating / charging temperature for the DHW.
Value:
Set the temperature.
* See Appendix "Parameter ID overview"
MENU > Settings > Tank temperature
Stop difference
Circuit
All
Set the number of degrees below the desired DHW temperature, but
measured by the lower tank temperature sensor that will stop the DHW
heating / charging.
NOTE: If condition for stop, related to the lower DHW tank temperature
sensor, is present, the stop is done when the upper DHW tank temperature
sensor has a temperature 2 K higher than the start difference level.
* See Appendix "Parameter ID overview"
Value:
Set the number of degrees.
56
DEN-SMT/DK
ECL Comfort 310, application P318
1x152
Setting range
Factory setting
*
1x194
Factory setting
Setting range
*
NOTE:
The desired DHW temperature will be reduced if "Max. charge T" is
lower than (Desired DHW temp. + Charge difference).
*
Example:
Desired DHW temp. =
Charge difference =
Max. charge T =
Result:
Desired DHW temp. will be reduced to 45 °C.
*
VI.JM.Q3.02
50 °C
10 K
55 °C