MENU > Settings > Tank temperature
MENU > Settings > Refill tank
Start difference
Circuit
All
Set the number of degrees below the desired DHW temperature that will
start the DHW heating (charging).
* See Appendix "Parameter ID overview"
Value:
Set the number of degrees.
MENU > Settings > Tank temperature
Pump start diff.
Circuit
All
Charging pump P2 is switched ON when supply temperature S2 gets higher
than ('Desired buffer temperature' + 'Pump start diff. ' ).
Example: 60 °C + 3 K = 63 °C
* See Appendix "Parameter ID overview"
58
DEN-SMT/DK
ECL Comfort 310, application P318
1x195
Setting range
Factory setting
*
1x371
Setting range
Factory setting
*
Example:
Desired DHW temp.:
Start difference:
Result:
*
The DHW heating starts when the temperature measured by the tank
temperature sensor (upper) is lower than 52 °C.
*
VI.JM.Q3.02
55 °C
-3 K