Operating Guide
MENU > Settings > Control par., fan
MENU > Settings > Control par., inlet
MENU > Settings > Control par., outlet
MENU > Settings > Control par. 1
MENU > Settings > Control par. 2
MENU > Settings > Control par. 3
MENU > Settings > Control par., P circ.
MENU > Settings > Control par., P refill
V out max.
Circuit
All
The output voltage can be limited to a maximum value.
* See Appendix "Parameter ID overview"
The value in % expresses the maximum voltage for the output in
question.
MENU > Settings > Control par., fan
MENU > Settings > Control par., inlet
MENU > Settings > Control par., outlet
MENU > Settings > Control par. 1
MENU > Settings > Control par. 2
MENU > Settings > Control par. 3
MENU > Settings > Control par., P circ.
MENU > Settings > Control par., P refill
V out min.
Circuit
All
The output voltage can be limited to a minimum value.
* See Appendix "Parameter ID overview"
The value in % expresses the minimum voltage for the output in
question.
MENU > Settings > Control par. 1
MENU > Settings > Control par. 2
MENU > Settings > Control par. 3
Reverse out
Circuit
All
Valid only when the internal I / O module ECA 35 is used:
The analog output (0-10 volt) can be a rising or a falling voltage for rising
temperature demand. Also the PWM signal can be reversed.
* See Appendix "Parameter ID overview"
OFF:
The analog output voltage will rise at a rising
temperature demand.
The PWM signal will rise in % at a rising temperature
demand.
ON:
The analog output voltage will fall at a rising temperature
demand.
The PWM signal will fall in % at a rising temperature
demand.
Danfoss District Energy
ECL Comfort 310, application P318
1x165
Setting range
Factory setting
*
1x167
Setting range
Factory setting
*
1x171
Setting range
Factory setting
*
Example
A setting of 60% means that the output voltage will be 6 volt as a
maximum.
*
Example:
A setting of 20% means that the output voltage will be 2 volt as a
minimum.
The setting 'Reverse out' has no influence on the 'V out max' or 'V
out min' settings.
*
The 'V out min' setting has higher priority than 'V out max'.
*
VI.JM.Q3.02
DEN-SMT/DK
69