Supply T - Danfoss ECL Comfort 310 Operating Manual

Hide thumbs Also See for ECL Comfort 310:
Table of Contents

Advertisement

Operating Guide

6.5 Supply T

MENU > Event > Tank temp.
MENU > Event > Supply T
Event priority 20
Circuit
All
The event number and priority possibilities.
P318.1:
The event can be activated if the supply temperature S2 has been lower than
the desired charging temperature at S3 for more than the set "Delay" time.
P318.10:
The event can be activated if the supply temperature S2 has been lower than
the desired DHW flow temperature at S3 for more than the set "Delay" time.
* See Appendix "Parameter ID overview"
0
Log of event not active
1
Log of event in list
2
Log of event in list and notice (letter symbol in display)
3
Log of event in list and alarm (bell symbol in display and
activation of alarm output)
MENU > Event> Supply T
Delay
Circuit
All
If the supply temperature S2 is not acceptable* for more than the set "Delay"
(in minutes), the event is registered.
* P318.1: S2 lower than ('Desired buffer temperature' + 'Pump start diff. ' ).
Example: 60 °C + 3 K = 63 °C.
P318.10: S2 lower than the desired DHW flow temperature at S3.
* See Appendix "Parameter ID overview"
Parameters indicated with an ID no. like "1x607" mean a universal
parameter.
x stands for circuit / parameter group.
90
DEN-SMT/DK
ECL Comfort 310, application P318
9020
Setting range
Factory setting
*
1x340
Setting range
Factory setting
*
*
*
VI.JM.Q3.02
Danfoss District Energy