Operating Guide
MENU > Event > Charge T
MENU > Event > Tank temperature
MENU > Event > DHW flow T
MENU > Event > Supply T
Delay
Circuit
All
If an event from either 'Upper difference' or 'Lower difference' is present for a
longer time than the set delay (in minutes), the event is registered.
* See Appendix "Parameter ID overview"
Value:
The event will be present if the alarm condition remains
after the set delay.
MENU > Event > Charge T
MENU > Event > Tank temperature
MENU > Event > DHW flow T
MENU > Event > Supply T
Lowest temp.
Circuit
All
The event will not be registered if the desired temperature is lower than
the set value.
* See Appendix "Parameter ID overview"
Danfoss District Energy
ECL Comfort 310, application P318
1x149
Factory setting
Setting range
*
1x150
Setting range
Factory setting
*
Delay, example
Y
*
=
X
Time
=
Y
Temperature
=
# 1 #
Lower difference
=
# 2 #
Desired temperature
=
# 3 #
Actual temperature
=
# 4 #
Delay (ID 1x149)
If the cause of the event disappears, the event indication and, possibly,
the alarm output will also disappear.
*
VI.JM.Q3.02
#
1 #
# 2 #
# 3 #
#
4 #
X
DEN-SMT/DK
83