GE UR series Instruction Manual page 525

L60 line phase comparison system
Hide thumbs Also See for UR series:
Table of Contents

Advertisement

APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 15 of 55)
ADDR
REGISTER NAME
4706
Breaker 1 close
4707
Breaker 1 phase A / three-pole closed
4708
Breaker 1 phase B closed
4709
Breaker 1 phase C closed
470A
Breaker 1 external alarm
470B
Breaker 1 alarm delay
470D
Breaker 1 pushbutton control
470E
Breaker 1 manual close recall time
4710
Breaker 1 out of service
4711
Breaker 1 block open
4712
Breaker 1 block close
4713
Breaker 1 phase A / three-pole opened
4714
Breaker 1 phase B opened
4715
Breaker 1 phase C opened
4716
Breaker 1 operate time
4717
Breaker 1 events
4718
Reserved
4719
...Repeated for breaker 2
4732
...Repeated for breaker 3
474B
...Repeated for breaker 4
Synchrocheck (Read/Write Setting) (2 modules)
47A0
Synchrocheck 1 Function
47A1
Synchrocheck 1 V1 Source
47A2
Synchrocheck 1 V2 Source
47A3
Synchrocheck 1 Maximum Voltage Difference
47A5
Synchrocheck 1 Maximum Angle Difference
47A6
Synchrocheck 1 Maximum Frequency Difference
47A7
Synchrocheck 1 Dead Source Select
47A8
Synchrocheck 1 Dead V1 Maximum Voltage
47A9
Synchrocheck 1 Dead V2 Maximum Voltage
47AA
Synchrocheck 1 Live V1 Minimum Voltage
47AB
Synchrocheck 1 Live V2 Minimum Voltage
47AC
Synchrocheck 1 Target
47AD
Synchrocheck 1 Events
47AE
Synchrocheck 1 Block
47AF
Synchrocheck 1 Frequency Hysteresis
47B0
...Repeated for Synchrocheck 2
Flexcurves A and B (Read/Write Settings)
4800
FlexCurve A (120 items)
48F0
FlexCurve B (120 items)
Modbus User Map (Read/Write Setting)
4A00
Modbus Address Settings for User Map (256 items)
User Displays Settings (Read/Write Setting) (16 modules)
4C00
User-Definable Display 1 Top Line Text
4C0A
User-Definable Display 1 Bottom Line Text
4C14
Modbus Addresses of Display 1 Items (5 items)
4C19
Reserved (7 items)
4C20
...Repeated for User-Definable Display 2
4C40
...Repeated for User-Definable Display 3
4C60
...Repeated for User-Definable Display 4
4C80
...Repeated for User-Definable Display 5
4CA0
...Repeated for User-Definable Display 6
4CC0
...Repeated for User-Definable Display 7
4CE0
...Repeated for User-Definable Display 8
GE Multilin
RANGE
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 1000000
0 to 1
0 to 1000000
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 2
0 to 1
---
0 to 1
0 to 5
0 to 5
0 to 400000
0 to 100
0 to 2
0 to 5
0 to 1.25
0 to 1.25
0 to 1.25
0 to 1.25
0 to 2
0 to 1
0 to 65535
0 to 0.1
0 to 65535
0 to 65535
0 to 65535
---
---
0 to 65535
---
L60 Line Phase Comparison System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
s
0.001
F003
---
1
F102
s
0.001
F003
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
s
0.001
F001
---
1
F102
---
---
---
---
1
F102
---
1
F167
---
1
F167
V
1
F060
degrees
1
F001
Hz
0.01
F001
---
1
F176
pu
0.01
F001
pu
0.01
F001
pu
0.01
F001
pu
0.01
F001
---
1
F109
---
1
F102
---
1
F300
Hz
0.01
F001
ms
1
F011
ms
1
F011
---
1
F001
---
---
F202
---
---
F202
---
1
F001
---
---
F001
DEFAULT
0
0
0
0
0
B
0
0 (Disabled)
0
0
0
0
0
0
0
70
0 (Disabled)
---
0 (Disabled)
0 (SRC 1)
1 (SRC 2)
10000
30
100
1 (LV1 and DV2)
30
30
70
70
0 (Self-reset)
0 (Disabled)
0
6
0
0
0
" "
""
0
0
B-23