GE UR series Instruction Manual page 615

L60 line phase comparison system
Hide thumbs Also See for UR series:
Table of Contents

Advertisement

APPENDIX D
<21> := Measured value, normalized value without quantity descriptor
<30> := Single-point information with time tag CP56Time2a
<31> := Double-point information wiht time tag CP56Time2a
<32> := Step position information with time tag CP56Time2a
<33> := Bitstring of 32 bits with time tag CP56Time2a
<34> := Measured value, normalized value with time tag CP56Time2a
<35> := Measured value, scaled value with time tag CP56Time2a
<36> := Measured value, short floating point value with time tag CP56Time2a
<37> := Integrated totals with time tag CP56Time2a
<38> := Event of protection equipment with time tag CP56Time2a
<39> := Packed start events of protection equipment with time tag CP56Time2a
<40> := Packed output circuit information of protection equipment with time tag CP56Time2a
Either the ASDUs of the set <2>, <4>, <6>, <8>, <10>, <12>, <14>, <16>, <17>, <18>, and <19> or of the set
<30> to <40> are used.
Process information in control direction
<45> := Single command
<46> := Double command
<47> := Regulating step command
<48> := Set point command, normalized value
<49> := Set point command, scaled value
<50> := Set point command, short floating point value
<51> := Bitstring of 32 bits
<58> := Single command with time tag CP56Time2a
<59> := Double command with time tag CP56Time2a
<60> := Regulating step command with time tag CP56Time2a
<61> := Set point command, normalized value with time tag CP56Time2a
<62> := Set point command, scaled value with time tag CP56Time2a
<63> := Set point command, short floating point value with time tag CP56Time2a
<64> := Bitstring of 32 bits with time tag CP56Time2a
Either the ASDUs of the set <45> to <51> or of the set <58> to <64> are used.
System information in monitor direction
<70> := End of initialization
System information in control direction
<100> := Interrogation command
<101> := Counter interrogation command
<102> := Read command
<103> := Clock synchronization command (see Clause 7.6 in standard)
<104> := Test command
<105> := Reset process command
<106> := Delay acquisition command
<107> := Test command with time tag CP56Time2a
GE Multilin
L60 Line Phase Comparison System
D.1 PROTOCOL
M_ME_ND_1
M_SP_TB_1
M_DP_TB_1
M_ST_TB_1
M_BO_TB_1
M_ME_TD_1
M_ME_TE_1
M_ME_TF_1
M_IT_TB_1
M_EP_TD_1
M_EP_TE_1
M_EP_TF_1
C_SC_NA_1
C_DC_NA_1
C_RC_NA_1
C_SE_NA_1
C_SE_NB_1
C_SE_NC_1
C_BO_NA_1
C_SC_TA_1
C_DC_TA_1
C_RC_TA_1
C_SE_TA_1
C_SE_TB_1
C_SE_TC_1
C_BO_TA_1
M_EI_NA_1
C_IC_NA_1
C_CI_NA_1
C_RD_NA_1
C_CS_NA_1
C_TS_NA_1
C_RP_NA_1
C_CD_NA_1
C_TS_TA_1
D
D-3

Advertisement

Table of Contents
loading

Table of Contents