GE UR series Instruction Manual page 239

L60 line phase comparison system
Hide thumbs Also See for UR series:
Table of Contents

Advertisement

5 SETTINGS
a) MAIN MENU
PATH: SETTINGS
GROUPED ELEMENTS
PHASE COMPARISON
ELEMENTS
MESSAGE
MESSAGE
MESSAGE
b) 87PC SCHEME
PATH: SETTINGS
GROUPED ELEMENTS
87PC SCHEME
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin
PHASE COMPARISON ELEMENTS
87PC SCHEME
ADVANCED
FAULT DETECTORS
CHARGE CURRENT
COMPENSATION
OPEN BREAKER
ECHO
SETTING GROUP 1(6)
PHASE COMPARISON ELEMENTS
87PC FUNCTION:
Disabled
87PC SCHEME SELECT:
2TL-TR-SPC-2FC
87PC BLOCK:
Off
87PC SIGNAL SOURCE:
One Source Current
87PC SIGNAL:
Mixed I_2-K*I_1
87PC MIXED SIGNAL K:
0.20
87PC MIXED SIGNAL
REF ANGLE: 0°
87PC FDL PICKUP:
0.50 pu
87PC FDL AUX:
Off
87PC FDH PICKUP:
0.75 pu
87PC FDH AUX:
Off
87PC FDH SUPV:
Off
87PC CH1 ASYMMETRY:
0.0 ms
87PC CH2 ASYMMETRY:
0.0 ms
87PC CH1 DELAY:
0.0 ms
L60 Line Phase Comparison System
5.5 GROUPED ELEMENTS
5.5.3 PHASE COMPARISON ELEMENTS
See page 5–107.
See page 5–115.
See page 5–121.
See page 5–123.
87PC SCHEME
Range: Disabled, Enabled
Range: 2TL-TR-SPC-2FC, 2TL-BL-SPC-2FC,
2TL-TR-DPC-3FC, etc.
Range: FlexLogic™ operand
Range: One Source Current, Two Sources Current
Range: Mixed I_2–K*I_1, 3I_0
Range: 0.00 to 0.25 in steps of 0.01
Range: 0 to 359° in steps of 1
Range: 0.02 to 15.00 pu in steps of 0.01
Range: FlexLogic™ operand
Range: 0.05 to 15.00 pu in steps of 0.01
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: –5.0 to 5.0 ms in steps of 0.1
Range: –5.0 to 5.0 ms in steps of 0.1
Range: 0.0 to 30.0 ms in steps of 0.1
5
5-107