Display Properties - GE UR series Instruction Manual

L60 line phase comparison system
Hide thumbs Also See for UR series:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
If this setting is "On" (the default setting), then remote setting access functions as normal; that is, a remote password is
required). If this setting is "Off", then remote setting access is blocked even if the correct remote setting password is
provided. If this setting is any other FlexLogic™ operand, then the operand must be asserted (set as on) prior to pro-
viding the remote setting password to gain setting access.
ACCESS AUTH TIMEOUT: This setting represents the timeout delay for local setting access. This setting is applicable
when the
LOCAL SETTING AUTH
and is continuously monitored for an off-to-on transition. When this occurs, local access is permitted and the timer pro-
grammed with the
immediately denied. If access is permitted and an off-to-on transition of the FlexLogic™ operand is detected, the time-
out is restarted. The status of this timer is updated every 5 seconds.
The following settings are available through the remote (EnerVista UR Setup) interface only. Select the Settings > Product
Setup > Security menu item to display the security settings window.
The Remote Settings Authorization setting is used for remote (Ethernet or RS485 interfaces) setting access supervision.
If this setting is "On" (the default setting), then remote setting access functions as normal; that is, a remote password is
required). If this setting is "Off", then remote setting access is blocked even if the correct remote setting password is pro-
vided. If this setting is any other FlexLogic™ operand, then the operand must be asserted (set as on) prior to providing the
remote setting password to gain setting access.
5
The Access Authorization Timeout setting represents the timeout delay remote setting access. This setting is applicable
when the Remote Settings Authorization setting is programmed to any operand except "On" or "Off". The state of the
FlexLogic™ operand is continuously monitored for an off-to-on transition. When this occurs, remote setting access is per-
mitted and the timer programmed with the Access Authorization Timeout setting value is started. When this timer
expires, remote setting access is immediately denied. If access is permitted and an off-to-on transition of the FlexLogic™
operand is detected, the timeout is restarted. The status of this timer is updated every 5 seconds.
PATH: SETTINGS
PRODUCT SETUP
DISPLAY
PROPERTIES
5-12
setting is programmed to any operand except "On". The state of the FlexLogic™ oper-
setting value is started. When this timer expires, local setting access is
ACCESS AUTH TIMEOUT

DISPLAY PROPERTIES

LANGUAGE:
English
FLASH MESSAGE
MESSAGE
TIME:
1.0 s
DEFAULT MESSAGE
MESSAGE
TIMEOUT: 300 s
DEFAULT MESSAGE
MESSAGE
INTENSITY: 25 %
SCREEN SAVER
MESSAGE
FEATURE: Disabled
SCREEN SAVER WAIT
MESSAGE
TIME: 30 min
CURRENT CUT-OFF
MESSAGE
LEVEL: 0.020 pu
VOLTAGE CUT-OFF
MESSAGE
LEVEL: 1.0 V
L60 Line Phase Comparison System
5.2.2 DISPLAY PROPERTIES
Range: English; English, French; English, Russian;
English, Chinese
(range dependent on order code)
Range: 0.5 to 10.0 s in steps of 0.1
Range: 10 to 900 s in steps of 1
Range: 25%, 50%, 75%, 100%
Visible only if a VFD is installed
Range: Disabled, Enabled
Visible only if an LCD is installed
Range: 1 to 65535 min. in steps of 1
Visible only if an LCD is installed
Range: 0.002 to 0.020 pu in steps of 0.001
Range: 0.1 to 1.0 V secondary in steps of 0.1
5 SETTINGS