5 SETTINGS
c) BREAKER FLASHOVER
PATH: SETTINGS
CONTROL ELEMENTS
BREAKER
FLASHOVER 1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The detection of the breaker flashover is based on the following condition:
1.
Breaker open,
2.
Voltage drop measured from either side of the breaker during the flashover period,
3.
Voltage difference drop, and
4.
Measured flashover current through the breaker.
Furthermore, the scheme is applicable for cases where either one or two sets of three-phase voltages are available across
the breaker.
GE Multilin
MONITORING ELEMENTS
BKR 1 FLSHOVR
FUNCTION: Disabled
BKR 1 FLSHOVR SIDE 1
SRC: SRC 1
BKR 1 FLSHOVR SIDE 2
SRC: None
BKR 1 STATUS CLSD A:
Off
BKR 1 STATUS CLSD B:
Off
BKR 1 STATUS CLSD C:
Off
BKR 1 FLSHOVR V PKP:
0.850 pu
BKR 1 FLSHOVR DIFF V
PKP: 1000 V
BKR 1 FLSHOVR AMP
PKP: 0.600 pu
BKR 1 FLSHOVR PKP
DELAY: 0.100 s
BKR 1 FLSHOVR SPV A:
Off
BKR 1 FLSHOVR SPV B:
Off
BKR 1 FLSHOVR SPV C:
Off
BKR 1 FLSHOVR BLOCK:
Off
BKR 1 FLSHOVR
TARGET: Self-reset
BKR 1 FLSHOVR
EVENTS: Disabled
L60 Line Phase Comparison System
5.6 CONTROL ELEMENTS
BREAKER FLASHOVER 1(2)
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: None, SRC 1, SRC 2, SRC 3, SRC 4
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: 0.000 to 1.500 pu in steps of 0.001
Range: 0 to 100000 V in steps of 1
Range: 0.000 to 1.500 pu in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled