Iec 61850 Goose Analogs - GE UR series Instruction Manual

L60 line phase comparison system
Hide thumbs Also See for UR series:
Table of Contents

Advertisement

5.7 INPUTS/OUTPUTS
UR-1
SETTING
TELEPROT OUTPUT 1-1:
(same for 1-2...1-16)
Off (Flexlogic Operand)
SETTING
TELEPROT INPUT 1-1
DEFAULT:
(same for 1-2...1-16)
FLEXLOGIC OPERAND
TELEPRO INPUT 1-1 On
OR
(same for 1-2...1-16)
SETTING
TELEPROT OUTPUT 2-1:
(same for 1-2...1-16)
Off (Flexlogic Operand)
SETTING
TELEPROT INPUT 2-1
DEFAULT:
(same for 1-2...1-16)
FLEXLOGIC OPERAND
TELEPRO INPUT 2-1 On
OR
(same for 1-2...1-16)
5
PATH: SETTINGS
INPUTS/OUTPUTS
GOOSE ANALOG
INPUT 1
The IEC 61850 GOOSE analog inputs feature allows the transmission of analog values between any two UR-series
devices. The following settings are available for each GOOSE analog input.
ANALOG 1 DEFAULT: This setting specifies the value of the GOOSE analog input when the sending device is offline
and the
ANALOG 1 DEFAULT MODE
point number. Because of the large range of this setting, not all possible values can be stored. Some values may be
rounded to the closest possible floating point number.
ANALOG 1 DEFAULT MODE: When the sending device is offline and this setting is "Last Known", the value of the
GOOSE analog input remains at the last received value. When the sending device is offline and this setting value is
"Default Value", then the value of the GOOSE analog input is defined by the
GOOSE ANALOG 1 UNITS: This setting specifies a four-character alphanumeric string that can is used in the actual
values display of the corresponding GOOSE analog input value.
GOOSE ANALOG 1 PU: This setting specifies the per-unit base factor when using the GOOSE analog input FlexAna-
log™ values in other L60 features, such as FlexElements™. The base factor is applied to the GOOSE analog input
FlexAnalog quantity to normalize it to a per-unit quantity. The base units are described in the following table.
5-266
ACTUAL VALUES
CHANNEL 1 STATUS:
On
Fail
Off
OK
ACTUAL VALUES
CHANNEL 2 STATUS:
On
Fail
Off
OK
Figure 5–143: TELEPROTECTION INPUT/OUTPUT PROCESSING

IEC 61850 GOOSE ANALOGS

ANALOG
1000.000
ANALOG
MESSAGE
MODE: Default Value
GOOSE ANALOG
MESSAGE
UNITS:
GOOSE ANALOG
MESSAGE
is set to "Default Value".This setting is stored as an IEEE 754 / IEC 60559 floating
L60 Line Phase Comparison System
ACTUAL VALUES
CHANNEL 1 STATUS:
Communication channel #1
(Teleprotection I/O Enabled)
ACTUAL VALUES
CHANNEL 2 STATUS:
Communication channel #2
(On 3-terminal system or 2-terminal
with redundant channel)
GOOSE ANALOG INPUT 1(16)
Range: –1000000.000 to 1000000.000 in steps of 0.001
1 DEFAULT:
Range: Default Value, Last Known
1 DEFAULT
Range: up to 4 alphanumeric characters
1
Range: 0.000 to 1000000000.000 in steps of 0.001
1 PU:
1.000
5 SETTINGS
UR-2
SETTING
TELEPROT INPUT 1-1
DEFAULT:
(same for 1-2...1-16)
On
FLEXLOGIC OPERAND
Fail
Off
TELEPRO INPUT 1-1 On
OR
OK
(same for 1-2...1-16)
SETTING
TELEPROT OUTPUT 1-1:
(same for 1-2...1-16)
Off (Flexlogic Operand)
UR-2 or UR-3
SETTING
TELEPROT INPUT 2-1
DEFAULT:
(same for 2-2...2-16)
On
FLEXLOGIC OPERAND
Fail
Off
TELEPRO INPUT 2-1 On
OR
OK
(same for 2-2...2-16)
SETTING
TELEPROT OUTPUT 2-1:
(same for 2-2...2-16)
Off (Flexlogic Operand)
5.7.12 IEC 61850 GOOSE ANALOGS
setting.
ANALOG 1 DEFAULT
842750A2.CDR