GE UR series Instruction Manual page 539

L60 line phase comparison system
Hide thumbs Also See for UR series:
Table of Contents

Advertisement

APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 29 of 55)
ADDR
REGISTER NAME
730B
dcmA Inputs 1 Units
730E
dcmA Inputs 1 Range
730F
dcmA Inputs 1 Minimum Value
7311
dcmA Inputs 1 Maximum Value
7313
Reserved (5 items)
7318
...Repeated for dcmA Inputs 2
7330
...Repeated for dcmA Inputs 3
7348
...Repeated for dcmA Inputs 4
7360
...Repeated for dcmA Inputs 5
7378
...Repeated for dcmA Inputs 6
7390
...Repeated for dcmA Inputs 7
73A8
...Repeated for dcmA Inputs 8
73C0
...Repeated for dcmA Inputs 9
73D8
...Repeated for dcmA Inputs 10
73F0
...Repeated for dcmA Inputs 11
7408
...Repeated for dcmA Inputs 12
7420
...Repeated for dcmA Inputs 13
7438
...Repeated for dcmA Inputs 14
7450
...Repeated for dcmA Inputs 15
7468
...Repeated for dcmA Inputs 16
7480
...Repeated for dcmA Inputs 17
7498
...Repeated for dcmA Inputs 18
74B0
...Repeated for dcmA Inputs 19
74C8
...Repeated for dcmA Inputs 20
74E0
...Repeated for dcmA Inputs 21
74F8
...Repeated for dcmA Inputs 22
7510
...Repeated for dcmA Inputs 23
7528
...Repeated for dcmA Inputs 24
Disconnect switches (read/write settings)
7540
Disconnect switch 1 function
7541
Disconnect switch 1 name
7544
Disconnect switch 1 mode
7545
Disconnect switch 1 open
7546
Disconnect switch 1 block open
7547
Disconnect switch 1 close
7548
Disconnect switch 1 block close
7549
Disconnect switch 1 phase A / three-pole closed
754A
Disconnect switch 1 phase A / three-pole opened
754B
Disconnect switch 1 phase B closed
754C
Disconnect switch 1 phase B opened
754D
Disconnect switch 1 phase C closed
754E
Disconnect switch 1 phase C opened
754F
Disconnect switch 1 operate time
7550
Disconnect switch 1 alarm delay
7552
Disconnect switch 1 events
7553
Reserved (2 items)
7555
...Repeated for disconnect switch 2
756A
...Repeated for disconnect switch 3
757F
...Repeated for disconnect switch 4
7594
...Repeated for disconnect switch 5
75A9
...Repeated for disconnect switch 6
75BE
...Repeated for disconnect switch 7
75D3
...Repeated for disconnect switch 8
75E8
...Repeated for disconnect switch 9
GE Multilin
RANGE
---
0 to 6
-9999.999 to 9999.999
-9999.999 to 9999.999
0 to 65535
0 to 1
---
0 to 1
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 2
0 to 1000000
0 to 1
---
L60 Line Phase Comparison System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
---
F206
---
1
F173
---
0.001
F004
---
0.001
F004
---
1
F001
---
1
F102
---
---
F206
---
1
F157
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
s
0.001
F001
s
0.001
F003
---
1
F102
---
---
---
DEFAULT
"mA"
6 (4 to 20 mA)
4000
20000
0
B
0 (Disabled)
"SW 1"
0 (3-Pole)
0
0
0
0
0
0
0
0
0
0
70
0
0 (Disabled)
---
B-37

Advertisement

Table of Contents
loading