Signal Sources - GE UR series Instruction Manual

L60 line phase comparison system
Hide thumbs Also See for UR series:
Table of Contents

Advertisement

5 SETTINGS
PATH: SETTINGS
SYSTEM SETUP
SOURCE 1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
Identical menus are available for each source. The "SRC 1" text can be replaced by with a user-defined name appropriate
for the associated source.
The first letter in the source identifier represents the module slot position. The number directly following this letter repre-
sents either the first bank of four channels (1, 2, 3, 4) called "1" or the second bank of four channels (5, 6, 7, 8) called "5" in
a particular CT/VT module. Refer to the Introduction to AC sources section at the beginning of this chapter for additional
details on this concept.
It is possible to select the sum of all CT combinations. The first channel displayed is the CT to which all others will be
referred. For example, the selection "F1+F5" indicates the sum of each phase from channels "F1" and "F5", scaled to
whichever CT has the higher ratio. Selecting "None" hides the associated actual values.
The approach used to configure the AC sources consists of several steps; first step is to specify the information about each
CT and VT input. For CT inputs, this is the nominal primary and secondary current. For VTs, this is the connection type,
ratio and nominal secondary voltage. Once the inputs have been specified, the configuration for each source is entered,
including specifying which CTs will be summed together.
Table 5–6: SOURCE CONFIGURATION FOR PHASE COMPARISON
FUNCTION
SRC 1
Phase current
F1 to F3 CT channels
(used for 87PC first current
and Breaker Failure 1)
Ground current
F1 (Ground overcurrent)
Phase voltage
Not available
Auxiliary voltage
Not available
When two CTs are connected and configured with these settings, it is imperative that the CT rated secondary cur-
rent is identical for both CTs (that is, both CTs are 1 A rated or both CTs are 5 A rated).
NOTE
User selection of AC parameters for comparator elements:
CT/VT modules automatically calculate all current and voltage parameters from the available inputs. Users must select the
specific input parameters to be measured by every element in the relevant settings menu. The internal design of the ele-
ment specifies which type of parameter to use and provides a setting for source selection. In elements where the parameter
may be either fundamental or RMS magnitude, such as phase time overcurrent, two settings are provided. One setting
specifies the source, the second setting selects between fundamental phasor and RMS.
GE Multilin

SIGNAL SOURCES

SOURCE 1(2)
SOURCE 1 NAME:
SRC 1
SOURCE 1 PHASE CT:
None
SOURCE 1 GROUND CT:
None
SOURCE 1 PHASE VT:
None
SOURCE 1 AUX VT:
None
CT/VT MODULE 1 (TYPE 8P)
SRC 2
Not available
Not available
Not available
Not available
L60 Line Phase Comparison System
5.3 SYSTEM SETUP
5.3.3 SIGNAL SOURCES
Range: up to six alphanumeric characters
Range: None, F1, F5, F1+F5,... up to a combination of
any 6 CTs. Only Phase CT inputs are displayed.
Range: None, F1, F5, F1+F5,... up to a combination of
any 6 CTs. Only Ground CT inputs are displayed.
Range: None, F1, F5
Only phase voltage inputs will be displayed.
Range: None, F1, F5
Only auxiliary voltage inputs will be displayed.
CT/VT MODULE 2 (TYPE 8F)
SRC 3
L1 to L3 CT channels
Sum of F1:F3 and L1:L3
(used for 87PC second
(used for distance and
current and Breaker
Failure 2). This source is
configurable only if a
second CT/VT module is
ordered.
---
---
Three-phase line VT for
Single-phase bus VT for
synchrocheck
5
SRC 4
overcurrent)
---
distance and
synchrocheck
---
5-67