5.6 CONTROL ELEMENTS
If one or both sources are de-energized, the synchrocheck programming can allow for closing of the circuit breaker using
undervoltage control to by-pass the synchrocheck measurements (dead source function).
SYNCHK1 V1 SOURCE: This setting selects the source for voltage V1 (see NOTES below).
SYNCHK1 V2 SOURCE: This setting selects the source for voltage V2, which must not be the same as used for the
V1 (see NOTES below).
SYNCHK1 MAX VOLT DIFF: This setting selects the maximum primary voltage difference in volts between the two
sources. A primary voltage magnitude difference between the two input voltages below this value is within the permis-
sible limit for synchronism.
SYNCHK1 MAX ANGLE DIFF: This setting selects the maximum angular difference in degrees between the two
sources. An angular difference between the two input voltage phasors below this value is within the permissible limit
for synchronism.
SYNCHK1 MAX FREQ DIFF: This setting selects the maximum frequency difference in 'Hz' between the two sources.
A frequency difference between the two input voltage systems below this value is within the permissible limit for syn-
chronism.
SYNCHK1 MAX FREQ HYSTERESIS: This setting specifies the required hysteresis for the maximum frequency differ-
ence condition. The condition becomes satisfied when the frequency difference becomes lower than
. Once the Synchrocheck element has operated, the frequency difference must increase above the
FREQ DIFF
+
MAX FREQ DIFF
angle, remain satisfied).
SYNCHK1 DEAD SOURCE SELECT: This setting selects the combination of dead and live sources that will by-pass
synchronism check function and permit the breaker to be closed when one or both of the two voltages (V1 or/and V2)
are below the maximum voltage threshold. A dead or live source is declared by monitoring the voltage level. Six
5
options are available:
None:
LV1 and DV2:
DV1 and LV2:
DV1 or DV2:
DV1 Xor DV2:
DV1 and DV2:
SYNCHK1 DEAD V1 MAX VOLT: This setting establishes a maximum voltage magnitude for V1 in 1 'pu'. Below this
magnitude, the V1 voltage input used for synchrocheck will be considered "Dead" or de-energized.
SYNCHK1 DEAD V2 MAX VOLT: This setting establishes a maximum voltage magnitude for V2 in 'pu'. Below this
magnitude, the V2 voltage input used for synchrocheck will be considered "Dead" or de-energized.
SYNCHK1 LIVE V1 MIN VOLT: This setting establishes a minimum voltage magnitude for V1 in 'pu'. Above this mag-
nitude, the V1 voltage input used for synchrocheck will be considered "Live" or energized.
SYNCHK1 LIVE V2 MIN VOLT: This setting establishes a minimum voltage magnitude for V2 in 'pu'. Above this mag-
nitude, the V2 voltage input used for synchrocheck will be considered "Live" or energized.
5-216
SYNCHK1 MAX FREQ HYSTERESIS
Dead Source function is disabled
Live V1 and Dead V2
Dead V1 and Live V2
Dead V1 or Dead V2
Dead V1 exclusive-or Dead V2 (one source is Dead and the other is Live)
Dead V1 and Dead V2
L60 Line Phase Comparison System
sum to drop out (assuming the other two conditions, voltage and
5 SETTINGS
SYNCHK1 MAX
SYNCHK1
GE Multilin

Advertisement