GE UR series Instruction Manual page 240

L60 line phase comparison system
Hide thumbs Also See for UR series:
Table of Contents

Advertisement

5.5 GROUPED ELEMENTS
5
The phase comparison tripping scheme menu provides the main setup for the phase comparison relay.
87PC SCHEME SELECT: Selects the phase comparison element scheme logic as follows:
2TL-TR-SPC-2FC: two-terminal line, permissive tripping, single phase comparison, two frequency channel.
2TL-BL-SPC-2FC: two-terminal line, blocking scheme, single phase comparison, two frequency channel.
2TL-UB-DPC-2FC: two-terminal line, unblocking, dual phase comparison, two frequency channel (FSK PLC only);
scheme cannot be used for breaker-and-a-half applications.
2TL-TR-DPC-3FC:two-terminal line, permissive tripping, dual phase comparison, three frequency channel.
2TL-BL-DPC-3FC: three-terminal line, blocking scheme, dual phase comparison, three frequency channel.
5-108
87PC CH2 DELAY:
MESSAGE
0.0 ms
87PC CH1 RX VOLT:
MESSAGE
12.0 V
87PC CH2 RX VOLT:
MESSAGE
12.0 V
87PC TRIP SECURITY:
MESSAGE
First Coincidence
87PC SECOND COINCID
MESSAGE
TIMER: 40 ms
87PC STABILITY
MESSAGE
ANGLE:
75°
87PC ENHANCED STAB
MESSAGE
ANGLE: 110°
87PC PICKUP DELAY:
MESSAGE
0 ms
87PC STOP TX:
MESSAGE
Off
87PC TX RESET DELAY:
MESSAGE
0 ms
87PC RESET DELAY:
MESSAGE
30 ms
87PC TRANS BLOCK
MESSAGE
PICKUP: 0.030 s
87PC TRANS BLOCK
MESSAGE
RESET: 0.030 s
87PC CHNL LOSS TRIP
MESSAGE
WINDOW:
87PC HIGH-SPEED TRIP
MESSAGE
CONTACT 1: Off
87PC HIGH-SPEED TRIP
MESSAGE
CONTACT 2: Off
87PC TARGET:
MESSAGE
Self-Reset
87PC EVENTS:
MESSAGE
Disabled
L60 Line Phase Comparison System
Range: 0.0 to 30.0 ms in steps of 0.1
Range: 0.0 to 125.0 V in steps of 0.1
Range: 0.0 to 125.0 V in steps of 0.1
Range: First Coincidence, Enhanced
Range: 10 to 200 ms in steps of 1
Range: 40 to 140° in steps of 5
Range: 40 to 180° in steps of 5
Range: 0 to 50 ms in steps of 1
Range: FlexLogic™ operand
Range: 0 to 1000 ms in steps of 1
Range: 0 to 200 ms in steps of 1
Range: 0 to 65.535 s in steps of 0.001
Range: 0 to 65.535 s in steps of 0.001
Range: 0 to 500 ms in steps of 1
0 msec
Range: Off, available contact outputs
Range: Off, available contact outputs
Range: Self-Reset, Latched, Disabled
Range: Disabled, Enabled
5 SETTINGS
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents