5 SETTINGS
3.
Configure the data by making the following changes in the
COL
GGIO1 STATUS CONFIGURATION
Set
GGIO1 INDICATION 1
a contact input, virtual input, a protection element status, etc.).
The L60 must be rebooted (control power removed and re-applied) before these settings take effect.
The following procedure illustrates the reception configuration.
1.
Configure the reception dataset by making the following changes in the
61850 PROTOCOL
GSSE/GOOSE CONFIGURATION
1
CONFIG GSE 1 DATASET ITEMS
Set
to "GGIO3.ST.Ind1.q" to indicate quality flags for GGIO3 status indication 1.
ITEM 1
Set
to "GGIO3.ST.Ind1.stVal" to indicate the status value for GGIO3 status indication 1.
ITEM 2
The reception dataset now contains a set of quality flags, a single point status Boolean value, and a floating point ana-
log value. This matches the transmission dataset configuration above.
2.
Configure the GOOSE service settings by making the following changes in the
settings menu:
REMOTE DEVICE 1
Set
REMOTE DEVICE 1 ID
Set
REMOTE DEVICE 1 ETYPE APPID
"0" in the example above.
Set the
REMOTE DEVICE 1 DATASET
configurable GOOSE 1 in this example, program this value as "GOOSEIn 1".
3.
Configure the data by making the following changes in the
settings menu:
Set
REMOTE IN 1 DEVICE
Set
REMOTE IN 1 ITEM
item to remote input 1.
Remote input 1 can now be used in FlexLogic™ equations or other settings. The L60 must be rebooted (control power
removed and re-applied) before these settings take effect.
The value of remote input 1 (Boolean on or off) in the receiving device will be determined by the GGIO1.ST.Ind1.stVal value
in the sending device. The above settings will be automatically populated by the EnerVista UR Setup software when a com-
plete SCD file is created by third party substation configurator software.
For intercommunication between L60 IEDs, the fixed (DNA/UserSt) dataset can be used. The DNA/UserSt dataset contains
the same DNA and UserSt bit pairs that are included in GSSE messages. All GOOSE messages transmitted by the L60
(DNA/UserSt dataset and configurable datasets) use the IEC 61850 GOOSE messaging services (for example, VLAN sup-
port).
Set the
CONFIG GSE 1 FUNCTION
entered, return the
CONFIG GSE 1 FUNCTION
NOTE
PATH:...TRANSMISSION
CONFIGURABLE GOOSE 1(8)
CONFIG GSE 1
DATASET ITEMS
To create a configurable GOOSE dataset that contains an IEC 61850 Single Point Status indication and its associated qual-
ity flags, the following dataset items can be selected: "GGIO1.ST.Ind1.stVal" and "GGIO1.ST.Ind1.q". The L60 will then cre-
ate a dataset containing these two data items. The status value for GGIO1.ST.Ind1.stVal is determined by the FlexLogic™
operand assigned to GGIO1 indication 1. Changes to this operand will result in the transmission of GOOSE messages con-
taining the defined dataset.
GE Multilin
settings menu:
to a FlexLogic™ operand used to provide the status of GGIO1.ST.Ind1.stVal (for example,
RECEPTION
settings menu:
to match the GOOSE ID string for the transmitting device. Enter "GOOSEOut_1".
to match the ETHERTYPE application ID from the transmitting device. This is
value. This value represents the dataset number in use. Since we are using
to "GOOSEOut_1".
to "Dataset Item 2". This assigns the value of the GGIO3.ST.Ind1.stVal single point status
function to "Disabled" when configuration changes are required. Once changes are
to "Enabled" and restart the unit for changes to take effect.
CONIFIG GSE 1(64) DATA TIMES
ITEM 1:
GGIO1.ST.Ind1.stVal
L60 Line Phase Comparison System
PRODUCT SETUP
COMMUNICATION
PRODUCT SETUP
CONFIGURABLE GOOSE
INPUTS/OUTPUTS
INPUTS/OUTPUTS
REMOTE INPUTS
ITEM 1(64)
Range: all valid MMS data item references for
transmitted data
5.2 PRODUCT SETUP
IEC 61850 PROTO-
COMMUNICATION
IEC
CONFIGURABLE GOOSE
REMOTE DEVICES
5
REMOTE INPUT 1
5-25