5 SETTINGS
Table 5–4: RECOMMENDED SETTINGS FOR USER-PROGRAMMABLE LEDS
SETTING
PARAMETER
LED 1 operand
SETTING GROUP ACT 1
LED 2 operand
SETTING GROUP ACT 2
LED 3 operand
SETTING GROUP ACT 3
LED 4 operand
SETTING GROUP ACT 4
LED 5 operand
SETTING GROUP ACT 5
LED 6 operand
SETTING GROUP ACT 6
LED 7 operand
Off
LED 8 operand
Off
LED 9 operand
BREAKER 1 OPEN
LED 10 operand
BREAKER 1 CLOSED
LED 11 operand
BREAKER 1 TROUBLE
LED 12 operand
Off
Refer to the Control of setting groups example in the Control elements section of this chapter for group activation.
PATH: SETTINGS
PRODUCT SETUP
USER-PROGRAMMABLE
SELF TESTS
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
All major self-test alarms are reported automatically with their corresponding FlexLogic™ operands, events, and targets.
Most of the minor alarms can be disabled if desired.
When in the "Disabled" mode, minor alarms will not assert a FlexLogic™ operand, write to the event recorder, or display
target messages. Moreover, they will not trigger the
mode, minor alarms continue to function along with other major and minor alarms. Refer to the Relay self-tests section in
chapter 7 for additional information on major and minor self-test alarms.
To enable the Ethernet switch failure function, ensure that the
menu.
NOTE
GE Multilin
SETTING
LED 13 operand
LED 14 operand
LED 15 operand
LED 16 operand
LED 17 operand
LED 18 operand
LED 19 operand
LED 20 operand
LED 21 operand
LED 22 operand
LED 23 operand
LED 24 operand

USER-PROGRAMMABLE SELF TESTS

DIRECT RING BREAK
FUNCTION: Enabled
DIRECT DEVICE OFF
FUNCTION: Enabled
REMOTE DEVICE OFF
FUNCTION: Enabled
PRI. ETHERNET FAIL
FUNCTION: Disabled
SEC. ETHERNET FAIL
FUNCTION: Disabled
BATTERY FAIL
FUNCTION: Enabled
SNTP FAIL
FUNCTION: Enabled
IRIG-B FAIL
FUNCTION: Enabled
ETHERNET SWITCH FAIL
FUNCTION: Disabled
ANY MINOR ALARM
L60 Line Phase Comparison System
5.2 PRODUCT SETUP
PARAMETER
Off
BREAKER 2 OPEN
BREAKER 2 CLOSED
BREAKER 2 TROUBLE
SYNC 1 SYNC OP
SYNC 2 SYNC OP
Off
Off
AR ENABLED
AR DISABLED
AR RIP
AR LO
5.2.11 USER-PROGRAMMABLE SELF TESTS
Range: Disabled, Enabled. Valid for units equipped with
Direct Input/Output module.
Range: Disabled, Enabled. Valid for units equipped with
Direct Input/Output module.
Range: Disabled, Enabled. Valid for units that contain a
CPU with Ethernet capability.
Range: Disabled, Enabled. Valid for units that contain a
CPU with a primary fiber port.
Range: Disabled, Enabled. Valid for units that contain a
CPU with a redundant fiber port.
Range: Disabled, Enabled.
Range: Disabled, Enabled. Valid for units that contain a
CPU with Ethernet capability.
Range: Disabled, Enabled.
Range: Disabled, Enabled.
or
messages. When in the "Enabled"
ANY SELF-TEST
ETHERNET SWITCH FAIL FUNCTION