5.4 FLEXLOGIC™
Table 5–9: L60 FLEXLOGIC™ OPERANDS (Sheet 3 of 8)
OPERAND TYPE
OPERAND SYNTAX
ELEMENT:
Dig Element 1 PKP
Digital elements
Dig Element 1 OP
Dig Element 1 DPO
Dig Element 2 to Dig Element 48
ELEMENT:
FxE 1 PKP
FlexElements™
FxE 1 OP
FxE 1 DPO
FxE 2 to FxE 8
ELEMENT:
GND DIST Z1 PKP
Ground distance
GND DIST Z1 OP
GND DIST Z1 OP A
GND DIST Z1 OP B
GND DIST Z1 OP C
GND DIST Z1 PKP A
GND DIST Z1 PKP B
GND DIST Z1 PKP C
GND DIST Z1 SUPN IN
GND DIST Z1 DPO A
GND DIST Z1 DPO B
GND DIST Z1 DPO C
GND DIST Z2 DIR SUPN
GND DIST Z2 to Z3
ELEMENT:
GROUND IOC1 PKP
Ground
GROUND IOC1 OP
instantaneous
GROUND IOC1 DPO
overcurrent
GROUND IOC2
5
ELEMENT:
GROUND TOC1 PKP
Ground time
GROUND TOC1 OP
overcurrent
GROUND TOC1 DPO
GROUND TOC2
ELEMENT
LATCH 1 ON
Non-volatile latches
LATCH 1 OFF
LATCH 2 to LATCH 16
ELEMENT:
LINE PICKUP OP
Line pickup
LINE PICKUP PKP
LINE PICKUP DPO
LINE PICKUP I<A
LINE PICKUP I<B
LINE PICKUP I<C
LINE PICKUP UV PKP
LINE PICKUP LEO PKP
LINE PICKUP RCL TRIP
ELEMENT:
LOAD ENCHR PKP
Load encroachment
LOAD ENCHR OP
LOAD ENCHR DPO
ELEMENT:
NEG SEQ DIR OC1 FWD
Negative-sequence
NEG SEQ DIR OC1 REV
directional
NEG SEQ DIR OC2 FWD
overcurrent
NEG SEQ DIR OC2 REV
ELEMENT:
NEG SEQ IOC1 PKP
Negative-sequence
NEG SEQ IOC1 OP
instantaneous
NEG SEQ IOC1 DPO
overcurrent
NEG SEQ IOC2
ELEMENT:
NEG SEQ OV1 PKP
Negative-sequence
NEG SEQ OV1 DPO
overvoltage
NEG SEQ OV1 OP
NEG SEQ OV2...
ELEMENT:
NEG SEQ TOC1 PKP
Negative-sequence
NEG SEQ TOC1 OP
time overcurrent
NEG SEQ TOC1 DPO
NEG SEQ TOC2
5-88
OPERAND DESCRIPTION
Digital Element 1 is picked up
Digital Element 1 is operated
Digital Element 1 is dropped out
Same set of operands as shown for Dig Element 1
FlexElement™ 1 has picked up
FlexElement™ 1 has operated
FlexElement™ 1 has dropped out
Same set of operands as shown for FxE 1
Ground distance zone 1 has picked up
Ground distance zone 1 has operated
Ground distance zone 1 phase A has operated
Ground distance zone 1 phase B has operated
Ground distance zone 1 phase C has operated
Ground distance zone 1 phase A has picked up
Ground distance zone 1 phase B has picked up
Ground distance zone 1 phase C has picked up
Ground distance zone 1 neutral is supervising
Ground distance zone 1 phase A has dropped out
Ground distance zone 1 phase B has dropped out
Ground distance zone 1 phase C has dropped out
Ground distance zone 2 directional is supervising
Same set of operands as shown for GND DIST Z1
Ground instantaneous overcurrent 1 has picked up
Ground instantaneous overcurrent 1 has operated
Ground instantaneous overcurrent 1 has dropped out
Same set of operands as shown for GROUND IOC 1
Ground time overcurrent 1 has picked up
Ground time overcurrent 1 has operated
Ground time overcurrent 1 has dropped out
Same set of operands as shown for GROUND TOC1
Non-volatile latch 1 is ON (Logic = 1)
Non-voltage latch 1 is OFF (Logic = 0)
Same set of operands as shown for LATCH 1
Line pickup has operated
Line pickup has picked up
Line pickup has dropped out
Line pickup detected phase A current below 5% of nominal
Line pickup detected phase B current below 5% of nominal
Line pickup detected phase C current below 5% of nominal
Line pickup undervoltage has picked up
Line pickup line end open has picked up
Line pickup operated from overreaching zone 2 when reclosing the line
(zone 1 extension functionality)
Load encroachment has picked up
Load encroachment has operated
Load encroachment has dropped out
Negative-sequence directional overcurrent 1 forward has operated
Negative-sequence directional overcurrent 1 reverse has operated
Negative-sequence directional overcurrent 1 forward has operated
Negative-sequence directional overcurrent 1 reverse has operated
Negative-sequence instantaneous overcurrent 1 has picked up
Negative-sequence instantaneous overcurrent 1 has operated
Negative-sequence instantaneous overcurrent 1 has dropped out
Same set of operands as shown for NEG SEQ IOC1
Negative-sequence overvoltage element has picked up
Negative-sequence overvoltage element has dropped out
Negative-sequence overvoltage element has operated
Same set of operands as shown for NEG SEQ OV1
Negative-sequence time overcurrent 1 has picked up
Negative-sequence time overcurrent 1 has operated
Negative-sequence time overcurrent 1 has dropped out
Same set of operands as shown for NEG SEQ TOC1
L60 Line Phase Comparison System
5 SETTINGS
GE Multilin